4. Heat Insulation of Refrigerant Pipe
In order to prevent faults caused by condensate of the refrigerant pipe and drain pipe, perform
condensate prevention and heat insulation properly. If it is forecast that high humidity and
temperature environment (Condensate temperature is over 23°C) may exist in the ceiling, e.g., inside
the ceiling with slab, ceiling which is in the same environment as the outdoor air. It is necessary to
apply 10mm or thicker adiabatic wool (16~20kg/m
2
) to the refrigerant pipe and the drain pipe in
addition to applying the general heat insulation materials. Enough heat insulation materials should
also be applied to the refrigerant joint and the pipe joint.
Note: the heat insulation of drain pipe refer to the installation of indoor unit.
Please use heat-resistant materials as heat insulation material of the air-side pipe. (e.g., EPT)
Cover heat insulation materials separately at the liquid side and the air side. Moreover, perform
heat insulation thoroughly for the air-side pipes of the indoor unit, and prevent water from
dripping outside the unit.
After applying the auxiliary heat insulation materials, use vinyl resin tape to seal refrigerant pipe
and drainage pipe to prevent water leak.
5. Electric Connection
5.1 Caution
Use special power supply for the air conditioner. Design power supplies specific to the indoor
unit and outdoor unit. The supply voltage must comply with the nominal voltage.
The external supply circuit of the air conditioner must have a ground wire, and the power supply
ground wire of the indoor unit must be connected with the external ground wire firmly.
The wiring must be performed by professional technicians according to the circuit diagram
labels.
Distribute the wires according to the relevant electric technical standards promulgated by the
State, and set the Residual Current-operated Circuit Breaker (RCCB) properly.
Summary of Contents for MCCU-03CN1
Page 19: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 19 MCCU 07CN1 MCCU 10CN1 ...
Page 20: ...DM17 03 01 56_en Midea R410A 50Hz T1 Compressor Condensing Unit 20 MCCU 14CN1 MCCU 16CN1 ...
Page 23: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 23 MCCU 70CN1 MCCU 105CN1 ...
Page 26: ...DM17 03 01 56_en Midea R410A 50Hz T1 Compressor Condensing Unit 26 MCCU 45CN1 ...
Page 31: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 31 MCCU 45CN1 ...
Page 33: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 33 MCCU 105CN1 ...
Page 77: ...Midea R410A 50Hz T1 Compressor Condensing Unit DM17 03 01 56_en 77 Hi pressure protection ...
Page 78: ...DM17 03 01 56_en Midea R410A 50Hz T1 Compressor Condensing Unit 78 Low pressure protection ...