21
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way
valve
Connect the charge hose which you
disconnected from the vacuum pump to the
valve at the bottom of the cylinder. If the
refrigerant is R410A, make the cylinder bottom
up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge
set and charge the system with liquid refrigerant
If the system cannot be charge with the
specified amount of refrigerant, or can be
charged with a little at a time (approximately
150g each time) , operating the air conditioner
in the cooling cycle; however, one time is not
sufficient, wait approximately 1 minute and then
repeat the procedure.
5).When the electronic scale displays the
proper weight, disconnect the charge hose from
the 3-way valve’s service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner,
turn off the air conditioner before disconnecting
the hose.
6). Mounted the valve stem caps and the
service port. Use torque wrench to tighten the
service port cap to a torque of 18N.m. Be sure
to check for gas leakage.
Summary of Contents for MCHS-09NIH1
Page 11: ...9 6 Wiring Diagram 6 1 Indoor Unit MEHS 09NiH1 MEHS 12NiH1 MEHS 09NiH2 MEHS 12NiH2 MEHS 18NiH2...
Page 12: ...10 MEHS 22NiH2...
Page 13: ...11 6 2 Outdoor Unit MCHS 09NiH1 MCHS 12NiH1...
Page 14: ...12 MCHS 09NiH2 MCHS 12NiH2...
Page 15: ...13 MCHS 18NiH2 MCHS 22NiH2...
Page 16: ...14 For MCHS 12NiH2 For MCHS 09NiH1 MCHS 12NiH1...
Page 17: ...15 For MCHS 09NiH2 For MCHS 18NiH2...
Page 18: ...16 For MCHS 22NiH2...
Page 50: ...48 P W P N...