71
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation will not cause
converse water flow and the slope of the
branch pipes can be adjusted freely
The false installation will cause converse
water flow and the slope of the branch pipe
cannot be adjusted.
6. Water storage pipe setting
If the indoor unit has high extra static
pressure and without water pump to
elevate the condensate water, such as high
extra static pressure duct unit , the water
storage pipe should be set to avoid
converse flow or blow water phenomena.
Indoor
unit
More than 50mm
More than 25mm
Plug
Water storage pipe
7. Lifting pipe setting of indoor unit with
water pump
The length of lifting pipe should not exceed
the pump head of indoor unit water pump.
The drainage pipe should be set down
inclined after the lifting pipe immediately to
avoid wrong operation of water level switch.
Refer the following picture for installation
reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe
≤
150mm
B: Lift height
≤
the pump head of water pump
Down incline pipe
B
8. Blowhole setting
For the concentrated drainage pipe system,
there should design a blowhole at the
highest point of main pipe to ensure the
condensate water discharge smoothly.
The air outlet shall face down to prevent dirt
entering pipe.
Each indoor unit of the system should be
installed it.
The installation should be considering the
convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
9. The end of drainage pipe shall not
contact with ground directly.
12.5.3 Drainage test
12.5.3.1. Water leakage test
After finishing the construction of drainage pipe
system, fill the pipe with water and keep it for
24 hours to check whether there is leakage at
joint section.
12.5.3.2. Water discharge test
1. Natural drainage mode(the indoor unit with
outdoor drainage pump)
Infuse above 600ml water through water test
hole slowly into the water collector, observe
whether the water can discharge through the
transparent hard pipe at drainage outlet.
Summary of Contents for MCHSU-09PHH2
Page 7: ...5 2 2 Part names of Indoor Outdoor units Cassette Unit...
Page 8: ...6 Duct Units...
Page 9: ...7 Console...
Page 10: ...8 Ceiling floor Units...
Page 28: ...26 Console Unit Ceiling floor Units 39 37 39 37in 3 94in 39 37in 1 38in...
Page 32: ...30 MEHSU 09CHN2 MEHSU 12CHN2 MEHSU 36CSC2 MEHSU 48CSC2...
Page 33: ...31 MEHSU 36CSD2 MEHSU 48CSD2...
Page 34: ...32 MEHSU 18CHF2 MEHSU 24CHF2 MEHSU 36CSF2...
Page 35: ...33 MEHSU 48CSF2 MEHSU 36CSF2 MEHSU 48CSF2...
Page 36: ...34 6 2 Outdoor Unit MCHSU 09PHH2 MCHSU 12PHH2 MCHSU 18PHH2...
Page 37: ...35 MCHSU 24PHH2...
Page 38: ...36 MCHSU 36CSH2...
Page 41: ...39 For MCHSU 48CSH2...
Page 44: ...42 MEHSU 09CHD2 Code 0 Code 1 Code 2 Code 3 Code 4...
Page 45: ...43 MEHSU 12CHD2 Code 0 Code 1 Code 2 Code 3 Code 4...
Page 46: ...44 MEHSU 18CHD2 Code 0 Code 1 Code 2 Code 3 Code 4...
Page 47: ...45 MEHSU 24CHD2 Code 0 Code 1 Code 2 Code 3 Code 4...
Page 48: ...46 MEHSU 36CSD2 Code 0 Code 1 Code 2 Code 3 Code 4...
Page 49: ...47 MEHSU 48CSD2 Code 0 Code 1 Code 2 Code 3 Code 4...
Page 58: ...56 12 Field Wiring 36K 48K...