MCAC-VTSM-2016-02 R410A All DC Inverter Mini VRF
Specifications & Performance 43
10. Operation Limits
Cooling
O
utdoor temper
at
ur
e
(
℃
D
B)
O
utdoor temper
at
ur
e
(
℃
W
B)
Heating
Indoor temperature ( WB)
Indoor temperature ( DB)
R
ange
for
cont
inuou
s operat
ion
R
ange for intermitt
ent
oper
at
ion
R
ange for
inter
mittent o
p
e
ra
ti
o
n
R
an
ge
f
or
c
on
ti
nu
ou
s operat
ion
Mode
Outdoor temp.
Indoor temp.
Room relative humidity
Cooling mode
-15°C ~ 46°C
17°C ~ 32°C
below 80%
Heating mode
-15°C ~ 27°C
≤
27°C
───
Notes:
1. If the unit is running outside the above condition, protective device will start, and even then the units take place abnormality
running.
2. These figures base on the operation conditions between indoor units and outdoor units: Equivalent pipe length is 5m, and
height difference is 0m.
Precaution:
The indoor relative humidity should be lower than 80%. If the air conditioner works in an environment with a relative humidity
higher than mentioned above, the surface of the air conditioner may condensate. In this case, it is recommended to set the air
speed of the indoor unit to high.