Floor Standing MFM
DM16-01.01.25en
Service manual
48
10.2.5 High temperature protection
of
condenser
10.2.6 High pressure protection
High temperature protection of condenser
Check the resistance of the temp. sensor
according to
Appendix 1
, is it normal?
Possible reason
1. Air or other gas in the refrigerant.
2. Heat exchanger is dirty
3. Outdoor fan or fan blade is defective
4. Outdoor unit is bad ventilation
5. Refrigerant is leakage
6. Outdoor PCB is defective
Replace the sensor
No
Yes