MCAC-2008-11 Air-cooled Modular Chiller
31
11. Troubleshooting
11.1 Failure & Protection Codes of the Module
Code Trouble
E0
Water-flow check trouble(wire controller and control board must be restarted when the trouble is displayed for
the third time)
E1
Power phases sequence failure
E2 Communication failure
E3
Total outlet water Temperature sensor failure (available for main unit)
E4
Plate heat exchanger outlet water Temperature sensor failure
E5
Condenser A tube Temperature sensor failure
E6
Condenser B tube Temperature sensor failure
E7 Outdoor
Temperature
sensor
failure
E8
System A compressor discharge gas Temperature sensor failure
E9
Water-flow check trouble(wire controller and control board can recover automatically when the trouble is
displayed for the first and second times
EA
The number of auxiliary unit checked by main unit decrease(only for wire controller)
EB
Prevent frostbite Temp. sensor of plate heat-exchanger A trouble
EC
Wire controller can not search the modules on line
ED
Data communication between wire controller and modules failure(only for wire controller)
EE
Communication between wire controller and computer failure(only for wire controller)
EF
Prevent frostbite Temp. sensor of plate heat-exchanger B trouble
P0
System A high-pressure protection or discharge gas Temperature protection
P1
System A low-pressure protection
P2
System B high-pressure protection or discharge gas Temperature protection
P3
System B low-pressure protection
P4
System A current protection
P5
System B current protection
P6
System A Condenser high-Temperature protection
P7
System B Condenser high-Temperature protection
P8
Digital compressor discharge Temperature protection, when it is above 125
℃
Pb
System anti-freeze protection
PC
Gas discharge Temp. of digital compressor above 125
℃
protection(only for wire controller)
PE Low-temperature
protection of plate heat-exchanger
11.2 Troubles and Solutions
Troubles Possible
reasons
Solutions
Air or other gas enter the system
Discharge the gas from refrigerant
charging hole, re-vacuuming if
necessary
Fins are dirty or jammed by some
obstacles
Splash the fins of condenser
The condenser wind flow is insufficient
or motor fail
Check the condenser motor, repair it if
necessary
High discharge pressure
(Cooling)
High suction pressure
Refer to the “high suction pressure”
part.
Summary of Contents for MGA-D30W/SN1
Page 23: ...MCAC 2008 11 Air cooled Modular Chiller 23 10 Exploded View 10 1 MGA F30W SN1...
Page 25: ...MCAC 2008 11 Air cooled Modular Chiller 25 10 2 MGA F65W SN1...
Page 27: ...MCAC 2008 11 Air cooled Modular Chiller 27 10 3 MGA D30W SN1...
Page 38: ...MCAC 2008 11 Air cooled Modular Chiller 38 Reference figure of water system installation...