R410A tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
108
2) Subordinate unit: (Water flow detection will not be done).
18
COM (I) 485 communication port (Fault code E2).
COM (O) is interconnected with P, Q and E of COM (I), used for RS-485 communication.
1) If faults occur between the wired controller and the main unit module, all modules will be shut down.
2) If faults occur between the main unit and subordinate units, the subordinate unit module suffering communication fault will
be shut down. Less units will be detected by the wired controller, which may display EC, and in the meanwhile, the indicator
lamp of the wired controller will flash.
Restart 3 minutes later after malfunction be removed.
19
COM (O) 485 communication port (Fault code E2).
20
Anti-freezing pressure protection in system A(Protection code Pc).
Anti-freezing pressure protection in system B(Protection code Pd).
21
The alarm signal output of the unit(ON/OFF signal).
22
Auxiliary electric heater:
Attention: the control port value of auxiliary electric heater actually detected is ON/OFF but not 220-240V control power
supply, so special attention should be paid when installing the auxiliary electric heater.
Attention!
Under heating mode, when the main unit board detects total water outlet temperature to be lower than 45
℃
, the switch will be
closed, and the auxiliary electric heater will begin to work; when the total water outlet temperature is higher than 50
℃
, the
switch will be opened, and the auxiliary electric heater will stop working.
23
PUMP.
Attention: the control port value of the pump actually detected is ON/OFF but not 220-240V control power supply, so special
attention should be paid when installing the pump.
1) After receiving start-up instruction, the pump will be started up instantly, and will maintain start-up state always in the
process of operation.
2) In case of refrigerating or heating shutdown, the pump will be shut down 2 minutes after all modules stop operating.
3) In case of shutdown under the pump mode, the pump can be directly shut down.
24
S2 ON: Cooling only OFF
:
R&C
S3 ON: Digital OFF
:
Fixed
S4 ON:H-EEprom OFF
:
Normal
S5 ON:C-EEprom OFF
:
Normal
25
One compressor of the system B.
Four-way valve of the system B.
One compressor of the system A.
Four-way valve of the system A.
26
8
9
A
B
C
D
E
F
8
7
6
5
4
3
2
1
0
When the address is 0, it serves as the main
unit.
Summary of Contents for MGBT-F120W/PN1
Page 28: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 29 60kW module ...
Page 29: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 30 120kW module ...
Page 30: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 31 180kW module ...
Page 32: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 33 60kW module ...
Page 33: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 34 120kW module ...
Page 34: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 35 180kW module ...
Page 36: ......
Page 46: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 47 ...
Page 48: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 49 MGCT D30W PN1 ...
Page 49: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 50 ...
Page 51: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 52 10 2 MGBT F60W PN1 ...
Page 54: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 55 ...
Page 55: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 56 ...
Page 57: ...R410A tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 58 10 4 MGBT F180W PN1 ...
Page 82: ...MCAC ATSM 2014 09 R410A tropical air cooled scroll chiller unit 60Hz 83 ...