Specification
MCAC-TSM-2008-02
56
Installation
5. Error code Er30:
Values display indication
Er30
Refer to the instruction manual: Frost prevention alarm.
Judge 1: Whether the unit has electric, because: When
water outlet temperature (T02)<4 , water pump and
℃
electric heater start working, when water outlet
temperature (T02)>6 , water pump and electric heater
℃
stop working.
Judge 2: Check whether the electric heater is well.
Supply the power.
No
Yes
Replace the electric heater
No
Yes
Judge 3: Check the water delivery sensor T02
has insert well.
No
Insert the water delivery sensor T02
well
Yes
Judge 4: Check the set temperature:
cooling= 10 heating = 45
℃
℃
Reset the point temperature
No
Judge 5: PCB is malfunction
Yes
Replace the PCB.
Summary of Contents for MGC-F05W/N1
Page 2: ......
Page 15: ...MCAC TSM 2008 02 Outdoor units Outdoor units 13 2 2 MGC F09W N1 MGC F10W N1 MGC F10W SN1...
Page 16: ...Specification MCAC TSM 2008 02 14 Installation 2 3 MGC F12W SN1 MGC F14W SN1 MGC F16W SN1...
Page 19: ...MCAC TSM 2008 02 Outdoor units Outdoor units 17 5 Wiring Diagrams 5 1 MGC F05W N1 MGC F07W N1...
Page 20: ...Specification MCAC TSM 2008 02 18 Installation 5 2 MGC F09W N1 MGC F10W N1...
Page 39: ...MCAC TSM 2008 02 Outdoor units Outdoor units 37 8 Operation Limits...
Page 42: ...Specification MCAC TSM 2008 02 40 Installation 10 Exploded View 10 1 MGC F05W N1...
Page 44: ...Specification MCAC TSM 2008 02 42 Installation 10 2 MGC F07W N1...
Page 46: ...Specification MCAC TSM 2008 02 44 Installation 10 3 MGC F09W N1 MGC F10W N1...
Page 48: ...Specification MCAC TSM 2008 02 46 Installation 10 4 MGC F10W SN1...
Page 50: ...Specification MCAC TSM 2008 02 48 Installation 10 5 MGC F12W SN1 MGC F16W SN1...
Page 52: ...Specification MCAC TSM 2008 02 50 Installation 10 6 MGC F14W SN1...
Page 86: ...Standard Controller MCAC TSM 2008 02 84 Controller 3 Select the Clock CL...
Page 89: ...MCAC TSM 2008 02 Standard Controller Controller 87...
Page 94: ...Standard Controller MCAC TSM 2008 02 92 Controller...