9. Error code Er20:
Values display indication
Er20
Refer to the instruction manual: Water flow protection.
Judge 1: Check whether the differential
pressure switch is close.
Close the differential
pressure switch
No
Yes
Judge 2: Check whether the pump is
setting high.
No
Setting the pump in high.
Yes
Judge 3: Check whether the air is in
water circuit,
Vent the air
Judge 4: Check whether the filter is
air-logged.
Clean the impurity.
Yes
No
Yes
Judge 5: Check whether the plate heat
exchanger is air-logged.
No
Clean the impurity.
Yes
Judge 6: PCB is malfunction
No
Replace PCB
Summary of Contents for MGC-F05W/N1
Page 2: ......
Page 15: ...MCAC TSM 2008 02 Outdoor units Outdoor units 13 2 2 MGC F09W N1 MGC F10W N1 MGC F10W SN1...
Page 16: ...Specification MCAC TSM 2008 02 14 Installation 2 3 MGC F12W SN1 MGC F14W SN1 MGC F16W SN1...
Page 19: ...MCAC TSM 2008 02 Outdoor units Outdoor units 17 5 Wiring Diagrams 5 1 MGC F05W N1 MGC F07W N1...
Page 20: ...Specification MCAC TSM 2008 02 18 Installation 5 2 MGC F09W N1 MGC F10W N1...
Page 39: ...MCAC TSM 2008 02 Outdoor units Outdoor units 37 8 Operation Limits...
Page 42: ...Specification MCAC TSM 2008 02 40 Installation 10 Exploded View 10 1 MGC F05W N1...
Page 44: ...Specification MCAC TSM 2008 02 42 Installation 10 2 MGC F07W N1...
Page 46: ...Specification MCAC TSM 2008 02 44 Installation 10 3 MGC F09W N1 MGC F10W N1...
Page 48: ...Specification MCAC TSM 2008 02 46 Installation 10 4 MGC F10W SN1...
Page 50: ...Specification MCAC TSM 2008 02 48 Installation 10 5 MGC F12W SN1 MGC F16W SN1...
Page 52: ...Specification MCAC TSM 2008 02 50 Installation 10 6 MGC F14W SN1...
Page 86: ...Standard Controller MCAC TSM 2008 02 84 Controller 3 Select the Clock CL...
Page 89: ...MCAC TSM 2008 02 Standard Controller Controller 87...
Page 94: ...Standard Controller MCAC TSM 2008 02 92 Controller...