Aqua Mini Full DC Inverter Unitary Chiller 50Hz
85
P1 malfunction: High pressure protection
LED displays P1
High pressure protection
Judge whether the wiring connection is correct.
Judge wire body is broken or not.
YES
NO
Connect again.
To confirm: short-circuit high pressure switch and check whether
the system can operate normally or not.
NO
Replace high pressure switch.
YES
Check whether the cooling system is normal or not.
Replace main PCB.
NO
Check whether pressure of the system is too high.
YES
Stop the system.
NO
Whether side air duct of outdoor unit meets the standard.
NO
Rectify the air duct
YES
Whether the heat exchanger needs cleaning.
YES
Clean.
NO
Whether the pipeline is blocked.
YES
Rectify the pipeline.
Judge the circulation water pump is damaged or not.
Repair or replace the water pump
YES
Whether plate heat exchanger is fouling or blocked severely
Clean or replace heat exchanger .
YES
NO
NO
Summary of Contents for MGRH10A-PA1Z
Page 16: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 16 7 Wiring Diagram MGRH5A PA1Z MGRH7A PA1Z...
Page 17: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 17 MGRH10A PA1Z...
Page 18: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 18 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...
Page 29: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 29 MGRH12A PA3Z MGRH14A PA3Z...
Page 30: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 30 MGRH16A PA3Z...
Page 32: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 32 13 Exploded View MGRH5A PA1Z MGRH7A PA1Z...
Page 34: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 34 MGRH10A PA1Z...
Page 36: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 36 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...