P5: Condenser high temperature protection
When condenser temperature is higher than 62 degrees, the unit will stop operating. When pipe temperature outside is
lower than 52 degrees, the unit will resume operate.
LED displays P5
Condenser high temperature protection
Check whether condenser temperature is higher than 62
degrees
NO
Check whether the resistance of condenser
temperature sensor is correct.
YES
Replace the outdoor main PCB.
NO
Replace the temperature sensor
YES
Whether outdoor temperature is too high(higher than 48
degrees)or not.
NO
Whether heat exchanger needs cleaning.
NO
Check if the EXV is blocked or not.
Clean heat exchanger
YES
YES
Replace EXV and then use high pressure
nitrogen to blow the pipe. Vacuumed the
pipe then add the refrigerant again.
YES
Stop the unit
NO
Replace outdoor main PCB.
Summary of Contents for MGRH10A-PA1Z
Page 16: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 16 7 Wiring Diagram MGRH5A PA1Z MGRH7A PA1Z...
Page 17: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 17 MGRH10A PA1Z...
Page 18: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 18 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...
Page 29: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 29 MGRH12A PA3Z MGRH14A PA3Z...
Page 30: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 30 MGRH16A PA3Z...
Page 32: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 32 13 Exploded View MGRH5A PA1Z MGRH7A PA1Z...
Page 34: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 34 MGRH10A PA1Z...
Page 36: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 36 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...