Capacity Tables MCAC-KTSM-2007-2
32 Compact Four Way Cassette Type
Cooling Capacity Table
Unit: W
Model
Water
inlet
temp.
(℃)
Water
FV
(LPM)
Water
PD
(kPa)
Air inlet condition
DB24
℃
DB25
℃
DB26
℃
DB27
℃
DB28
℃
WB17
℃
WB18
℃
WB19
℃
WB19.5
℃
WB21
℃
SH
TH
SH
TH
SH
TH
SH
TH
SH
TH
MKB-400
5
6
4.6
1852 2188 1911 2407 1961 2626 2062 2744 2062 3089
8
8.1
1970 2466 2037 2710 2096 2963 2205 3097 2222 3493
10
12.7
2045 2651 2121 2921 2197 3198 2298 3342 2331 3779
12
18.2
2121 2811 2197 3097 2273 3400 2382 3552 2424 4023
6
6
4.6
1784 2020 1835 2230 1894 2449 1995 2567 1995 2912
8
8.1
1885 2273 1953 2517 2012 2769 2121 2895 2138 3299
10
12.7
1843 1961 2028 2719 2104 2996 2214 3131 2239 3569
12
18.2
2020 2601 2104 2887 2180 3182 2289 3333 2331 3804
7
6
4.6
1709 1843 1768 2054 1818 2273 1919 2390 1919 2727
8
8.1
1801 2079 1869 2323 1936 2576 2037 2702 2054 3097
10
12.7
1869 2239 1944 2508 2012 2778 2121 3190 2155 3358
12
18.2
1927 2382 2003 2828 2087 3156 2197 3409 2230 3577
8
6
4.6
1633 1667 1692 1877 1751 2096 1852 2205 1852 2550
8
8.1
1717 1885 1784 2121 1852 2374 1953 2500 1978 2895
10
12.7
1776 2028 1852 2298 1927 2567 2037 2710 2062 3139
12
18.2
1826 2163 1911 2441 1986 2735 2104 2879 2138 3342
9
6
4.6
1566 1566 1624 1700 1675 1919 1776 2028 1784 2365
8
8.1
1641 1683 1709 1927 1776 2172 1877 2298 1894 2685
10
12.7
1692 1818 1860 2079 1835 2348 1944 2491 1978 2912
12
18.2
1734 1936 1818 2214 1894 2508 2012 2651 2045 3114
10
6
4.6
1431 1490 1549 1549 1608 1734 1709 1843 1717 2180
8
8.1
1557 1557 1624 1717 1692 1970 1801 2087 1818 2475
10
12.7
1599 1599 1675 1860 1751 2129 1860 2264 1894 2693
12
18.2
1641 1709 1725 1986 1801 2273 1919 2416 1961 2870
Remark
:
1. DB: Dry Bulb Temp. WB: Wet Bulb Temp. FV: Flow Volume
TH: Total heat SH: Sensible heat PD: Pressure Drop
2. Table above is based on normal type fan coil high speed air-flow volume; cooling capacity on other speed
air flow volume should multiply with corresponding capacity modification coefficient (refer to capacity
modification coefficient diagram.)