36
8.4 Operation Modes and Functions
8.4.1 Fan mode.
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules:
Once the compressor starts up, it will follow the below rules:
When indoor room temp.T1 is lower than Tn, the compressor and outdoor fan will shut off. When T1 is
higher than Tm, the compressor and outdoor fan will start up.
Tm=Ts ,Tn=Ts-2 for MSX-07HRN1-QC2, MSX-09HRN1-QC2,
MSX-12HRN1-QC2,
MSX-18HRN1-QC2 models.
Tm=Ts+1, Tn=Ts for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W model.
8.4.2.2 Outdoor fan running rules:
The On-off outdoor units have single fan speed. The outdoor fan will run following the compressor
except when AC is in evaporator high temp. protection in heating mode ,condenser high temp.