Indoor / outdoor units communication error diagnosis and solution
Yes
No
No
Change the indoor PCB
Change the outdoor PCB
Power on. Is the error extinguished
after 3 minutes?
Yes
Power on. Is the error extinguished
after 3 minutes?
Change the outdoor PCB
Yes
Change the indoor PCB
Yes
Power off, then power on the A/C by
the breaker.(reconnect the power
wire). Is the error extinguished?
Check the wiring on the outdoor
terminal
and
indoor
terminal
following the wiring diagram. Is all
the connecting correctly?
-24V<Vs<+24V?
(Vs is the voltage between S and N
of outdoor unit.)
No
Is the wiring to the outdoor PCB
connecting correctly?
Is the wiring to the indoor PCB
connecting correctly?
No