background image

 

 

40 

 

Condition of ending defrosting: 

If any one of the following items is satisfied, the defrosting will terminate and the machine will turn to 

normal heating mode. 

(1)  The defrosting time is reached to the setting value. 

(2)  The compressor current has reached or exceeded I

DEFROST 

for 7 seconds.

 

 

Defrosting action

 

 

About the setting defrosting time: 

(1)  Condition 1 of defrosting; 

If case B happens before case A and lasts till case A happens, the setting defrosting time is 10 minutes. 

Otherwise the defrosting time is 7.5 minutes. 

(2)  Condition 2 of defrosting. 

The defrosting time is 10 minutes. 

(3)  No matter what condition of the defrosting is, if the defrosting time keeps 7.5 minutes for 3 times, it 

will be 10 minutes in the 4

th

 defrosting. 

Summary of Contents for MOA-11HN1-QB8

Page 1: ...LUNA ON OFF SERIES Service Manual 2014 9ASEU B1 1401...

Page 2: ...6 3 Pipe length and the elevation 23 6 4 Installation for the first time 24 6 5 Adding the refrigerant after running the system for many years 27 6 6 Re installation while the indoor unit need to be r...

Page 3: ...mble or repair the product there is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is ri...

Page 4: ...y plug during operation There is risk of fire or electric shock Do not touch operation the product with wet hands Do not place a heater or other appliance near the power cable There is risk of fire an...

Page 5: ...er supply plug or turn off the breaker There is risk of product damage or failure or unintended operation Take care to ensure that nobody could step on or fall onto the outdoor unit This could result...

Page 6: ...door units Always insert the filter securely Clean the filter every two weeks or more often if necessary A dirty filter reduces the efficiency of the air conditioner and could cause product malfunctio...

Page 7: ...OA1 09HN1 QC2 MS9A 09HRN1 QC2 MOA3 09HN1 QC2 MS9A 09HRN1 QC7G MOB1 09HN1 QC7 11k MS9A 11HRN1 QB8 MOA 11HN1 QB8 12k MS9A 12HRN1 QC2 MOB1 12HN1 QC2 MS9A 12HRN1 QC2 MOB3 12HN1 QC2 MS9A 12HRN1 QC7G MOB 12...

Page 8: ...Filter O Bio Filter O Golden Fin O Cold catalyst filter Compressor Crankcase Heater O Self Clean O Follow me O 8 degree heating O Heat compensation O Self diag function Hydrophilic aluminum fin Anti...

Page 9: ...9A 07HRN1 QC2 MS9A 09HRN1 QC2 MS9A 09HRN1 QB8 MS9A 09HRN1 QB6 MS9A 09HRN1 QC7G 790 198 265 MS9A 11HRN1 QB8 MS9A 12HRN1 QC2 MS9A 16HRN1 QB8 A MS9A 12HRN1 QC7G 920 223 292 MS9A 16HRN1 QB6 MS9A 17HRN1 QC...

Page 10: ...m L mm H mm Dimension of installation hole mm MS9A 07HRN1 QB6 110 100 45 65 MS9A 07HRN1 QC2 MS9A 09HRN1 QB6 MS9A 09HRN1 QB8 MS9A 09HRN1 QC2 MS9A 09HRN1 QC7G 150 100 45 MS9A 11HRN1 QB8 MS9A 12HRN1 QC2...

Page 11: ...on of installation hole mm MS9A 18HRN1 QC5 120 100 45 65 MS9A 24HRN1 QB8W Model R mm L mm H mm Dimension of installation hole mm MS9A 12HRN1 QC7G 185 150 45 65 MS9A 16HRN1 QB6 MS9A 17HRN1 QC0 MS9A 18H...

Page 12: ...10 3 2 Outdoor Units More than 30cm More than 60cm More than 200cm More than 30cm More than 60cm Service space Fence or obstacles...

Page 13: ...09HN1 QC2 700 240 540 757 458 250 MOA3 09HN1 QC2 MOA 11HN1 QB8 MOB1 09HN1 QC7 780 250 540 843 549 276 MOB 12HN1 QC7 MOB3 16HN1 QB6 MOB1 12HN1 QC2 MOB3 12HN1 QC2 MOB1 18HN1 QB6 MOC 17HN1 QC0 760 285 5...

Page 14: ...R HEAT EXCHANGE CONDENSER COMPRESSOR 2 WAY VALVE 3 WAY VALVE 4 WAY VALVE COOLING HEATING T2 Evaporator temp sensor T1 Room temp sensor T3 Condenser temp sensor ACCUMULATOR INDOOR OUTDOOR CHECK VALVE H...

Page 15: ...Indoor Units MS9A 07HRN1 QB6 MS9A 07HRN1 QC2 MS9A 09HRN1 QB6 MS9A 09HRN1 QB8 MS9A 09HRN1 QC2 MS9A 09HRN1 QC7G MS9A 11HRN1 QB8 MS9A 12HRN1 QC2 MS9A 16HRN1 QB6 MS9A 16HRN1 QB8 A MS9A 17HRN1 QC0 MS9A 18H...

Page 16: ...14 MS9A 12HRN1 QC7G...

Page 17: ...15 MS9A 18HRN1 QC5...

Page 18: ...16 MS9A 24HRN1 QB8W...

Page 19: ...r Units MOK 07HN1 QB6 MOK1 07HN1 QB6 MOK1 07HN1 QC2 MOK1 09HN1 QB6 MOK 09HN1 QB8 MOA1 09HN1 QC2 MOA3 09HN1 QC2 MOB1 09HN1 QC7 MOA 11HN1 QB8 MOB 12HN1 QC7 MOB3 12HN1 QC2 MOB1 12HN1 QC2 MOB3 16HN1 QB6 M...

Page 20: ...18 MOC 17HN1 QC0...

Page 21: ...19 MOC 18HN1 QC0 MOF3 18HN1 QC5...

Page 22: ...20 MOP 24HN1 QB8W...

Page 23: ...21 MOF1 24HN1 QB8W...

Page 24: ...4 6500 663kgf cm 6700 683kgf cm 6 2 Connecting the cables The power cord of connect should be selected according to the following specifications sheet Rated current of appliance Nominal cross section...

Page 25: ...09HN1 QC7 MS9A 12HRN1 QC2 MOB1 12HN1 QC2 MS9A 11HRN1 QB8 MOA 11HN1 QB8 1 2 12 7 1 4 6 35 5 8 20 20 MS9A 12HRN1 QC2 MOB3 12HN1 QC2 MS9A 12HRN1 QC7G MOB 12HN1 QC7 MS9A 18HRN1 QB6 MOB1 18HN1 QB6 MS9A 16H...

Page 26: ...t brush to check for leakage of the connecting points of the piping If bubbles come out the pipes have leakage 1 Air purging with vacuum pump 1 Completely tighten the flare nuts of the indoor and outd...

Page 27: ...indicator is a little higher than the atmosphere pressure Then remove the charge hose from the 3 way valve 8 Fully open the 2 way valve and 3 way valve and securely tighten the cap of the 3 way valve...

Page 28: ...rant if the pipe length 5m Procedure 1 Connect the charge hose to the charging cylinder open the 2 way valve and the 3 way valve Connect the charge hose which you disconnected from the vacuum pump to...

Page 29: ...nnect the charge hose to the 3 way service port open the 2 way valve and the 3 way valve Connect the charge hose to the valve at the bottom of the cylinder If the refrigerant is R410A make the cylinde...

Page 30: ...e the indoor unit need to be repaired 1 Collecting the refrigerant into the outdoor unit Procedure 1 Confirm that both the 2 way and 3 way valves are set to the opened position Remove the valve stem c...

Page 31: ...y the refrigerant Procedure 1 Confirm that both the 2 way and 3 way valves are set to the closed position 2 Connect the charge set and a charging cylinder to the service port of the 3 way valve Leave...

Page 32: ...to use a torque wrench to tighten the service port cap to a torque 18N m Be sure to check the gas leakage 6 7 Re installation while the outdoor unit need to be repaired 1 Evacuation for the whole syst...

Page 33: ...Put the charging cylinder onto the electronic scale and record the weight 4 Open the valves Low side on the charge set and charge the system with liquid refrigerant If the system cannot be charge wit...

Page 34: ...32 6 Mounted the valve stem caps and the service port Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...

Page 35: ...t to operate abnormally 2 The room relative humidity should be less than 80 If the air conditioner operates beyond this figure the surface of the air conditioner may attract condensation Please set th...

Page 36: ...amp This lamp illuminates when the air conditioner is in operation Auto indication lamp Lights up during the Auto operation Timer indication lamp Lights up during Timer operation Defrost indication la...

Page 37: ...d outdoor fan will shut off B zone The current exceeds I5min for 5 minutes the compressor and outdoor fan will shut off C zone The current exceeds IFAN the outdoor fan will shut off if AC is in heatin...

Page 38: ...Medium 8 4 2 Cooling Mode 8 4 2 1 Compressor running rules Once the compressor starts up it will follow the below rules When indoor room temp T1 is lower than Tn the compressor and outdoor fan will sh...

Page 39: ...wer than TE5 for 5 minutes the compressor and outdoor fan will shut off When T2 is higher than TE6 the compressor and outdoor fan will restart up 8 4 2 5 Condenser high temperature T3 protection For M...

Page 40: ...s Indoor fan can be set to high med low auto when the compressor is on And when the compressor is off the indoor fan will run at low speed and the louver will locate at the anti cold wind angle Anti c...

Page 41: ...if any of the following items is satisfied 1 Both A and B are satisfied A The compressor keeps running for 40 minutes B The evaporator coil temp T2 Indoor room temp T1 meets the below table T2 T1 High...

Page 42: ...d IDEFROST for 7 seconds Defrosting action About the setting defrosting time 1 Condition 1 of defrosting If case B happens before case A and lasts till case A happens the setting defrosting time is 10...

Page 43: ...ST start defrosting Low TLDEFROST If indoor fan is in low speed and T2 T1 TLDEFROST start defrosting Breeze or stop If indoor fan is breezing or stopped start defrosting Capacity T2 T1 THDEFROST TMDEF...

Page 44: ...ied 1 If T3 TC1 and the compressor keeps running over 45 minutes Meanwhile T3 TC3 for 3minutes 2 After the last defrosting the time that the outdoor fan is off but the compressor is on in high T2 prot...

Page 45: ...ly mode AC will run in auto mode in the below cases 1 Pressing the forced auto button 2 If AC is off it will run in auto mode when the timer on function is active 3 After setting the mode AC will run...

Page 46: ...as below sequence Forced auto Forced cooling Off Forced cooling mode The compressor and outdoor fan keep running and the indoor fan runs at low speed After running for 30 minutes AC will turn to dryi...

Page 47: ...heat pump models when they are in heating the setting temperature decreases 1 be higher than 17 every one hour 2 hours later the the indoor fan is fixed as low speed Anti cold wind function has the p...

Page 48: ...er malfunctions being eliminated and anti cold wind being released Ionizer will be available again 8 4 10 8 Heating optional In heating operation the preset temperature of the air conditioner can be a...

Page 49: ...1 EEPROM error E4 Over current protection of the compressor occurs 4 times E5 Indoor room temperature sensor T1 open circuit or short circuit E6 Evaporator coil temperature sensor T2 open circuit or s...

Page 50: ...perates normally Find out the cause and have it solved For example check whether the fan is blocked or the bearing is broken Check the wires of fan motor Are all the connections good No Yes No Correct...

Page 51: ...dex2 1 Indoor AC Fan Motor Power on and set the unit running in fan mode at high fan speed After running for 15 seconds measure the voltage of pin1 and pin2 If the value of the voltage is less than 10...

Page 52: ...e connections between temperature sensor and PCB Are the connections good Correct the connections No Yes Yes Replace indoor or outdoor PCB Replace the sensor and c h e c k i f t h e p r o b l e m happ...

Page 53: ...re too high Does the outdoor unit has bad air circulation Yes No Check if the outdoor fan can run properly No Correct the connection of fan motor or replace the fan motor Yes Yes Check if the compress...

Page 54: ...indoor PCB Shut off the power supply and turn it on 5 seconds later Is it still displaying the error code 9 2 5 Zero crossing detection error diagnosis and solution Check if the connections and power...

Page 55: ...er reconnect the power wire Is the error still displaying after several minutes No Yes Change the outdoor main PCB Power on Is the error extinguished Check all the wirings between indoor and outdoor i...

Page 56: ...r Compressor discharge temp T5 sensor Measure the resistance value of each winding by using the multi meter Table1 Some frequently used R T data for T1 T2 T3 and T4 sensor Temperature 5 10 15 20 25 30...

Reviews: