Mission On-off
DM16-01.01.21en
26
Service
manual
7.3 Pipe length and the elevation
The pipe length and refrigerant amount:
Model
Pipe size
Standard
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas Liquid
MSMBA-07HRN1(W) / MOAB01-07HN1
3/8’’
(
Ф
9.52)
1/4’’
(
Ф
6.35)
5 8
20
20
MSMBA-09HRN1(W) / MOAB01-09HN1
3/8’’
(
Ф
9.52)
1/4’’
(
Ф
6.35)
5 8
20
20
MSMBB-12HRN1(W) / MOBA02-12HN1
1/2’’
(
Ф
12.7)
1/4’’
(
Ф
6.35)
5 8
20
20
MSMBC-19HRN1(W) / MOBA02-18HN1
1/2’’
(
Ф
12.7)
1/4’’
(
Ф
6.35)
5 10
25
20
MSMBD-24HRN1(W) / MOCA01-24HN1
5/8’’
(
Ф
15.9)
3/8’’
(
Ф
9.52)
5 10
25
40
Caution:
The capacity test is based on the standard length and the maximum permissive length is based on the
system reliability.