8.7.8  Rating capacity test function 

 

1) 

Set the indoor unit with remote controller as: high fan, 30

  in heating mode, then press “TURBO” 

button on controller 6 times or more within 10 seconds(make sure indoor unit receives these signals), the 

machine will turn into rating capacity test mode, the buzzer will make a “di” sound for 2 seconds 

continuously. Also, indoor fan will change to rating speed, the frequency of compressor will be fixed as 

rating value. Any condition of above is not satisfied, the machine can not be turned into rating capacity test 

mode. 

2) 

The machine will quit from the rating capacity test mode if running for 5 hours or changing fan 

speed or setting temperature. 

 

8.7.9    Turbo function in heating mode 

  Elevate current frequency(excluding F8) to a higher grade. If indoor fan is in low speed or pause caused by 

defrosting or anti-cold-wind function, frequency of compressor will not be elevated one grade until these limit 

has been released. 

1) 

Indoor fan changes to turbo speed and anti-cold-wind function is valid. 

2) 

After running for 30 minutes the machine will turn back to previous setting mode. 

 

on 

off 

on 

off 

on 

off 

on 

off 

compressor 

4-way valve 

outdoor fan 

indoor fan 

indoor fan breeze 10s 

90s 

100s 

no longer than 10 minutes 

30s 

F8 

Summary of Contents for MOF-24HDN1-QC2W

Page 1: ...SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL MOUNTED TYPE MSR1 24HRDN1 QC2W V1 0 Mar 2010...

Page 2: ...e installation 13 7 6 Re air purging Re installation 14 7 7 Balance refrigerant of the 2 way 3 way valves 15 7 8 Evacuation 16 7 9 Gas charging 17 8 Electronic function 18 8 1 Abbreviation 18 8 2 Disp...

Page 3: ...a defective installation stand It may cause injury accident or damage to the product Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall wi...

Page 4: ...directly It may cause corrosion on the product Corrosion particularly on the condenser and evaporator fins could cause product malfunction or inefficient operation Operational Do not expose the skin d...

Page 5: ...3 your skin or clothes wash it well with clean Do not use the remote of the batteries have leaked The chemical in batteries could cause burns or other health hazards...

Page 6: ...direction according to operation mode Turbo wind high med low breeze Restarting is for approx 3 minutes Prevent the water being frozen on evaporator by sensing the evaporator pipe temperature in cooli...

Page 7: ...ency at operation mode Hydrophilic aluminum fin It is only operated in the heating operation mode except defrosting operation Anti rust cabinet Valve protection cover 4 way valve control Made from ele...

Page 8: ...6 3 Dimension 3 1 Indoor Unit 3 2 Outdoor Unit MOF 24HDN1 QC2W Dimension Model W H D 24k 1030 313 221...

Page 9: ...45 41 Indoor unit Dimension W H D mm 1030 313 221 Packing W H D mm 1135 435 315 Net Gross weight Kg 14 19 Outdoor fan motor Model YDK55 6G Brand Welling Input W 103 76 Capacitor uF 2 5 Speed r min 840...

Page 10: ...8 5 Refrigerant cycle diagram...

Page 11: ...9 6 Wiring diagram 6 1 Indoor Unit...

Page 12: ...10 6 2 Outdoor Unit...

Page 13: ...16 0 3 8 9 52 5 10 25 40 Caution Capacity is based on standard length and maximum allowance length is base of reliability Oil trap should be installed per 5 7 meters 7 4 Air purging of the piping and...

Page 14: ...and then wait for one minute 5 Use torque wrench to tighten the service port cap to a torque of 1 8 kgf m 18N m 6 Set the 3 way valve to the opened position 7 Mounted the valve stem nuts to the 2 way...

Page 15: ...hose with the push pin to the gas service port 5 Air purging of the charge hose Open the low pressure valve on the charge set slightly to purge air from the charge hose 6 Set the 2 way valve to the cl...

Page 16: ...te repeat 3 times After purging the air use a torque wrench to tighten the flare nut to on the 2 way valve 4 Check the gas leakage Check the flare connections for gas leakage 5 Discharge the refrigera...

Page 17: ...ice port 3 Open the valves Low side on the charge set and discharge the refrigerant until the gauge indicates 0 05 to 0 1Mpa If there is no air in the refrigeration cycle the pressure when the air con...

Page 18: ...ved toward 0 1 Mpa 76 cmHg vacuum of 4 mmHg or less 3 Close the valve Low side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approximately 5 minutes after...

Page 19: ...fied amount of refrigerant if can be charged with a little at a time approximately 150g each time0 while operating the air conditioner in the cooling cycle however one time is not sufficient wait appr...

Page 20: ...8 2 2 LED display control function Pressing LED display button on remote controller will turn off all displays on indoor unit while pressing once again all displays will resume 8 3 Protection 8 3 1 Pr...

Page 21: ...cable will work 2 Preheating mode A weak current flows through the coil of compressor from the wiring terminal of compressor then the compressor is heated without operation 3 Preheating release condit...

Page 22: ...ler 6 times or more within 10 seconds make sure indoor unit receives these signals the machine will turn into rating capacity test mode the buzzer will make a di sound for 2 seconds continuously Also...

Page 23: ...changed The horizontal angle is the same as in cooling mode 8 6 2 Room overlow temperature protection In drying mode if room temperature is lower than 10 compressor will stop and not resume until roo...

Page 24: ...ed 8 7 2 Indoor fan speed can be set as high medium low or auto grade but anti cold wind function is preferential Auto fan action in heating mode 8 7 3 After start the operation frequency of compresso...

Page 25: ...ion 1 if the two items are satisfied then judges if T2 has descended for more than 5 if it has the machine starts defrosting or continues to judge T2 and will not defrost until T2 drops more than 5 Co...

Page 26: ...rating capacity test mode 2 The machine will quit from the rating capacity test mode if running for 5 hours or changing fan speed or setting temperature 8 7 9 Turbo function in heating mode Elevate c...

Page 27: ...essing the touch button continuously the unit will be turned off 8 9 3 In forced operation mode all general protections is available 8 9 4 In forced cooling mode the unit will run with fixed frequency...

Page 28: ...follow 1 After pressing ECONOMIC or SLEEP button on controller the machine will turn into sleep mode 2 When cooling the setting temperature rises 1 be lower than 30 every one hour 2 hour later the ris...

Page 29: ...pacitors in PCB and relative circuit in outdoor unit even shut down the power supply electricity power still are kept in capacitors do not forget to discharge the electricity power in capacitor Electr...

Page 30: ...munication protection E5 Open or short circuit of outdoor temperature sensor E6 Open or short circuit of indoor temperature sensor P0 Inverter module over strong current protection P1 Over voltage or...

Page 31: ...between indoor and outdoor unit Is the connection of L N S and GND good Is the GND connection on outdoor PCB good NO NO Reconnect and retest again Is the LED4 red on outdoor PCB bright and LED1 yello...

Page 32: ...nd compressor good Repair or correct the connector or connection Replace the outdoor PCB and then repower on Is the failure cleared NO YES Check the compressor NO Is the indoor temperature and evapora...

Page 33: ...ressor is it right YES Replace inverter compressor Reconnect and retry NO NO YES Does compressor operate Is the connection good Is refrigerant circulation volume normal NO NO Charge refrigerant Is abn...

Page 34: ...value of each winding by using the multi meter 9 3 2 Outdoor Fan Motor Model YDK55 6G Measure the resistance value of each winding by using the multi meter Position Resistance Value Blue Red 0 95 20 B...

Page 35: ...or Measure the resistance value of each winding by using the multi meter Some frequently used R T data for T1 T2 T3 and T4 sensor Temperature 5 10 15 20 25 30 40 50 60 Resistance Value K 26 9 20 7 16...

Reviews: