30
9.2.5 P0(Inverter module over-strong current protection) diagnosis and solution.
9.2.6 P1(over voltage or too low voltage protection) diagnosis and solution.
9.2.7 P2(temperature protection of compressor top) diagnosis and solution.
Is all connections on PCB
and between PCB and
compressor good?
Repair or correct the
connector or connection.
Replace the outdoor PCB
and then repower on. Is
the failure cleared?
NO
YES
Check the compressor
NO
Is the indoor temperature
and evaporator sensor
connector and connection
good?
Repair the connector and
reconnect
Replace the sensor and
check if E6 display again?
NO
YES
Replace the indoor PCB
YES
Is the power supply good?
Be sure the power supply is
normal when using the units
NO
YES
Replace the outdoor e-box.
Summary of Contents for MOF-24HDN1-QC2W
Page 10: ...8 5 Refrigerant cycle diagram...
Page 11: ...9 6 Wiring diagram 6 1 Indoor Unit...
Page 12: ...10 6 2 Outdoor Unit...