114
Does the condenser fan and indoor blower fan free without rubbing, and are they tight on the
shafts?
Are all covers and access panels in place to prevent air loss and safety hazards?
Starting the unit:
When the unit operates under cooling mode, please check the line voltage of the unit. The
voltage should be within the range shown on the unit nameplate.
If low voltage is encountered, check the size and the length of power supply wire from the mian
disconnect to the unit. The line may be undersized for the length of the run.
Shut-down the unit:
Place the system selector in the OFF position or reset thermostat (Wired controller) at a setting
above room temperature.
Do not de-energize the main power supply disconnect except when unit is to be serviced.
9. Safety control
Functions
Minutes delay for the compressor start-up:
At the beginning of energizing, 3-minutes delay should be taken to start the compressor. While
after the stop of the compressor, 7-minutes delay should be taken to restart the compressor.
Compressor discharge temperature protection:
When the temperature of compressor discharge is higher than 125°C (257°F), the compressor
will stop. Once the temperature is lower than 90°C (194°F), the compressor can be started
again.
Reverse phase protection relay:
The reverse phase protection relay will make the unit not start, when the power supply source is
in correctly conneted.
The checking of phase order is just carried out at the first time of electrifying. If malfunction
happens then the checking will be going on until the order of phase is right, and the error code
will be displayed on the board. If there is no problem in the first checking, then it will be omitted.
High pressure and low pressure protection :
Summary of Contents for MRC-062HWN1-R
Page 27: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 27...
Page 29: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 29...
Page 31: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 31...
Page 33: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 33...
Page 35: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 35...
Page 37: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 37 MRC 085HWN1 R C...
Page 38: ...MCAC RTT5 201707 Midea R410A ClimaCreator Series Rooftop Package 50Hz 38 MRC 100HWN1 R C...
Page 40: ...MCAC RTT5 201707 Midea R410A ClimaCreator Series Rooftop Package 50Hz 40 MRC 175HWN1 R C...
Page 41: ...Midea R410A ClimaCreator Series Rooftop Package 50Hz MCAC RTT5 201707 41 MRC 200HWN1 R C...