10.2.4 E3(indoor fan speed out of control) diagnosis and solution
10.2.5 E5(Open or short circuit of outdoor ambient or condenser temperature sensor) diagnosis and solution.
10.2.6 E6(open or short circuit of indoor room or evaporator temperature sensor) diagnosis and solution.
10.2.7 P0(IGBT over-strong current protection) diagnosis and solution.
Is all connections on PCB
and between PCB and
compressor good?
Repair or correct the
connector or connection.
Replace the outdoor PCB
and then repower on. Is
the failure cleared?
NO
YES
Check the compressor
NO
Is the indoor temperature
and evaporator sensor
connector and connection
good?
Repair the connector and
reconnect
Replace the sensor and
check if E6 display again?
NO
YES
Replace the.indoor PCB
YES
Is the outdoor temperature
sensor connector and
connection good?
Repair the connector and
reconnect
Replace the sensor and
check if E5 display again?
NO
YES
Replace outdoor e-box
YES
Is the indoor fan motor
connector and connection
good?
Repair the connector and
reconnect
Is voltage being applied to
the fan motor?
(rang 90v-160v between
mid pin and N on CN1
NO
YES
Indoor PCB is defective.
Replace the indoor PCB.
YES
Replace the indoor fan
motor
NO
Summary of Contents for MS9A-09HRDN1-QC2
Page 3: ...10 1 Indoor Unit Error Display 31 10 2 Diagnosis and Solution 32 10 3 Key parts checking 40...
Page 10: ...7 3 2 Outdoor Unit MOR 09 12HDN1 QC2...
Page 12: ...9 5 Refrigerant cycle diagram...
Page 13: ...10 6 Wiring diagram 6 1 Indoor Unit MS9A 09 12HRDN1 QC2...
Page 14: ...11 6 2 Outdoor Unit MOR 09 12HDN1 QC2...
Page 40: ...37...