Service manual
21
9. Pressure
table
Note:
The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.
D: Dry bulb temp.
W: Wet bulb temp.
9.1 MSV1-09HRDN1
Cooling mode
Outdoor temperature (Dry bulb temp)
Indoor Conditions
Pressure 25ºC 30ºC 35ºC 40ºC 45ºC
50ºC
21ºC D15ºC W
Pressure( kg/cm
2
) 8.7 8.9 8.9 9.0 10.0 10.6
24ºC D17ºC W
Pressure( kg/cm
2
) 8.8 8.9 8.9 9.6 10.5 11.0
27ºC D19ºC W Pressure( kg/cm
2
) 8.8
8.9
9.0
9.0
11.0 11.5
32ºC D23ºC W Pressure( kg/cm
2
) 8.9
9.0
9.1 10.1 12.0 12.5
Heating mode
OUTDOOR CONDITIONS
Indoor Conditions
Pressure
12ºC D
11ºC W
7ºC D
6ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
-7ºC D
-9ºC W
-15ºC D
-xºC W
15ºC Pressure(
kg/cm
2
) 34.0 33.5 32.0 31.0 28.0 27.0
18ºC Pressure(
kg/cm
2
) 35.0 34.5 34.0 32.5 29.0 27.5
20ºC Pressure(
kg/cm
2
) 36.5 36.0 35.5 33.5 30.0 28.5
22ºC Pressure(
kg/cm
2
) 37.0 36.5 36.0 35.0 31.5 29.0
9.2 MSV1-12HRDN1
Cooling mode
Outdoor temperature (Dry bulb temp)
Indoor Conditions
Pressure
25ºC
30ºC
35ºC
40ºC 45ºC 50ºC
21ºC D15ºC W Pressure( kg/cm
2
) 6.4 6.6 6.8 7.2 7.6 8.1
24ºC D17ºC W Pressure( kg/cm
2
) 6.6 6.9 7.0 7.6 8.2 8.7
27ºC D19ºC W Pressure( kg/cm
2
) 6.9 7.0 7.3 7.6 8.6 9.2
32ºC D23ºC W Pressure( kg/cm
2
) 6.9 7.4 7.6 8.1 9.4 9.8
Heating mode
OUTDOOR CONDITIONS
Indoor Conditions Pressure
12ºC D 7ºC D 0ºC D -4ºC D -7ºC D -15ºC D
15ºC Pressure(
kg/cm
2
)
36.0 35..0
34.5
30.0
29.0 28.0
18ºC Pressure(
kg/cm
2
)
33.0 34.0
33.5
30.0
28.5 27.5
20ºC Pressure(
kg/cm
2
)
34.0 33.0
31.0
30.5
29.0 26.0
22ºC Pressure(
kg/cm
2
)
32.5 31.5
31.0
29.0
28.0 25.5
Summary of Contents for MSV1-09HRDN1
Page 1: ...Cover MSV1 09HRDN1 MSV1 12HRDN1...
Page 4: ......
Page 11: ...Service manual 5 Refrigerant cycle diagram 7...
Page 14: ...Service manual 7 1 2 Indoor main PCB 10...
Page 15: ...Service manual 7 1 3 Outdoor main PCB 11...
Page 16: ...Service manual 7 1 4 Outdoor power PCB 12...
Page 17: ...Service manual 7 2 Wiring diagram 7 2 1 MSV1 09HRDN1 MSV1 12HRDN1 13...