Service manual
27
T<1.0
℃
High
Room temp. down
1.0
℃
<T<2.0
℃
Med.
T>2.0
℃
Low
11.6.6. Indoor evaporator high-temperature protection at heating mode
Condition (T= Indoor exchanger temp.) Compressor
T<48
℃
On
53
℃
<T<63
℃
Decrease frequency of compressor
T>63
℃
Off
11.6.7. The current protection
Model
Current
Compressor
I>19.0 A
Off
Current up
18000btu/h
15.0.A<I<19.0A Decrease frequency of compressor
I< 12.5A
On
I>18.5 A
Off
14.5A<I<18.5A
Decrease frequency of compressor
Current down 18000btu/h
I< 12.0A
On
11.6.8. The temp. compensation
Jump setting in indoor PCB
J2
On
On
Off
Off
J3
On
Off
On
Off
0
℃
-4
℃
-2
℃
0
℃
Δ
T
11.7. Defrosting operation (Available for heating only).
11.7.1 Defrosting condition:
11.7.1.1.
When outdoor temp. is more than 0
℃
,
Defrosting starts when meeting one of the following conditions,
a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more
than 40 minutes, and the temperature remains consecutively -4°c for more than 3 minutes,
b. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more
than 80 minutes, and the temperature remains consecutively -2°c for more than 3 minutes
11.7.1.2.
When outdoor temp. is less than 0
℃
,
Defrosting starts when meeting one of the following conditions,
a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more
than 40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
b. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more
than 40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
c. The temperature of indoor unit pipe decreases 5°c than before
11.7.1.3.
The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more
than 120 minutes, and the temperature remains consecutively -2°c for more than 3 minute
s
11.7.2 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
a. The defrost time has reached to 10 minutes.
b. When the temperature of outdoor heat exchanger rises up to 8°C and this continues for more than 80
seconds.
c. When the temperature of outdoor heat exchanger rises up to 12°C
Summary of Contents for MSV1-09HRDN1
Page 1: ...Cover MSV1 09HRDN1 MSV1 12HRDN1...
Page 4: ......
Page 11: ...Service manual 5 Refrigerant cycle diagram 7...
Page 14: ...Service manual 7 1 2 Indoor main PCB 10...
Page 15: ...Service manual 7 1 3 Outdoor main PCB 11...
Page 16: ...Service manual 7 1 4 Outdoor power PCB 12...
Page 17: ...Service manual 7 2 Wiring diagram 7 2 1 MSV1 09HRDN1 MSV1 12HRDN1 13...