Outdoor Unit 10
3. Capacity Correction Factor for Height Difference
Capacity(Btu/h)
12k
Pipe Length (m)
Cooling
5
10
20
25
Height difference
H (m)
Indoor Upper
than Outdoor
10
0.973
0.948
0.936
5
0.995
0.983
0.958
0.945
0
1.000
0.988
0.963
0.950
Outdoor Upper
than Indoor
-5
1.000
0.988
0.963
0.950
-10
0.988
0.963
0.950
Heating
5
10
15
20
Height difference
H (m)
Indoor Upper
than Outdoor
10
0.993
0.978
0.970
5
1.000
0.993
0.978
0.970
0
1.000
0.993
0.978
0.970
Outdoor Upper
than Indoor
-5
0.992
0.985
0.970
0.962
-10
0.977
0.962
0.955
Capacity(Btu/h)
18k
Pipe Length (m)
Cooling
5
10
20
30
Height difference
H (m)
Indoor Upper
than Outdoor
20
0.928
0.912
10
0.969
0.937
0.921
5
0.995
0.979
0.946
0.930
0
1.000
0.984
0.951
0.935
Outdoor Upper
than Indoor
-5
1.000
0.984
0.951
0.935
-10
0.984
0.951
0.935
-20
0.951
0.935
Heating
5
10
20
30
Height difference
H (m)
Indoor Upper
than Outdoor
20
0.982
0.976
10
0.994
0.982
0.976
5
1.000
0.994
0.982
0.976
0
1.000
0.994
0.982
0.976
Outdoor Upper
than Indoor
-5
0.992
0.986
0.974
0.968
-10
0.978
0.966
0.960
-20
0.959
0.953
Summary of Contents for MUEU-18HRFNX-QRD0W
Page 1: ...LIGHT COMMERCIAL INVERTER SERIES SM_LC GA _R410A_R32_3D INV_EU_NA_1811 SERVICE MANUAL...
Page 2: ......
Page 5: ......
Page 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 12: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Page 15: ...Model Reference 4 2 2 Outdoor Unit Outdoor Unit...
Page 19: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Page 21: ...IDU Compact Cassette 6 4 Service Place...
Page 44: ...Outdoor Unit 3 Panel Plate B30...
Page 45: ...Outdoor Unit 4 Panel Plate BA30...
Page 46: ...Outdoor Unit 5 Panel Plate CA30...
Page 47: ...Outdoor Unit 6 Panel Plate D30...
Page 48: ...Outdoor Unit 7 Panel Plate E30...
Page 49: ...Outdoor Unit 8 Panel Plate 590...
Page 50: ...Outdoor Unit 9 2 Service Place...
Page 62: ...Outdoor unit printed circuit board diagram 17122000002718...