V6-i VRF 50/60Hz
105
P
art
6
- Di
agno
si
s and
Tr
ou
bles
ho
o
ting
2.14
H7: Unmatched total number of indoor units
Digital display output
2.14.1
Description
2.14.2
Number of indoor units detected by the outdoor unit not same as number set on main PCB.
All units stop running.
Error code is displayed on the outdoor unit.
Trigger / recover condition
2.14.3
Trigger condition: Only one indoor unit cannot be detected by the outdoor unit for 8 hours or more than one indoor
unit cannot be detected by the outdoor unit for 3 minutes.
Recover condition: Number of indoor units detected by the outdoor unit is same as number set on main PCB.
Reset method: Resume automatically.
Possible causes
2.14.4
Number of indoor units set on main PCB not same as actual number of indoor units.
Some indoor units are powered off.
Communication wires between indoor and outdoor units not connected properly.
Indoor unit PCB damaged.
Indoor unit without address or indoor unit address duplicated.
Main PCB damaged.