P4, H6: Discharge temperature protection
Digital display output
2.19.1
;
Description
2.19.2
Discharge temperature protection.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
2.19.3
Trigger condition:
For P4 protection: Discharge temperature (T7C1/2) ≥ 120
o
C.
For H6 protection: P4 protection appears three times in 100 minutes.
Recover condition: Discharge temperature (T7C1/2) ≤ 90
o
C.
Reset method:
For P4 protection: Resume automatically.
For H6 protection: Manually restart.
Possible causes
2.19.4
Outdoor unit stop valves are closed.
Temperature sensor/switch not connected
properly or has malfunctioned.
Insufficient refrigerant.
System blockage.
Indoor load too large.
System contains air or nitrogen.
Poor condenser heat exchange.
Main PCB damaged.
Procedure
2.19.5
P4 / H6
ODU stop valves are closed
Yes
Open the stop valves
No
Compressor top temperature sensor,
discharge pipe temperature sensor
and/or discharge temperature switch
connections on main PCB are loose
1
Yes
Ensure the sensors and switch are
connected properly
No
Compressor top temperature sensor
and/or discharge pipe temperature
sensor have short circuited or failed
2
Yes
Replace the faulty sensor(s)
No
Flowchart continued on next page …
… flowchart continued from previous page