10.2 Troubleshooting
10.2.1 Open circuit or short circuit of temperature sensor diagnosis and solution(AS/E5/CS/oS/HS)
Error Code
AS/E5/CS/oS/HS
Malfunction decision
conditions
If the sampling voltage is lower than 0.06V or higher than 4.94V, the
LED will display the failure.
Supposed causes
●
Wiring mistake
●
Faulty
sensor
●
Faulty
PCB
Troubleshooting:
Check the connection
between temperature
sensor and PCB.
Correct the connection
No
Yes
Replace indoor main PCB
Measure the resistance
value of the sensor
Repalce the sensor
No
Yes
www.mideaaircon.com 25