V4+R VRF 50/60Hz
201702
27
P
art
3
- Con
tr
ol
5
Normal Operation Control
5.1
Component Control During Normal Operation
Table 3-5.1: Component control during normal cooling operation
Component
Wiring
diagram label
8-12HP
14-16HP
Control functions and states
Inverter compressor A
COMP(INV)
●
●
Controlled according to load requirement
Inverter compressor B
COMP(INV1)
●
DC fan motor A
FANA
●
●
Controlled according to discharge pressure
DC fan motor B
FANB
●
●
Electronic expansion valve A
EXVA
●
●
Position (steps) from 0 (fully closed) to 480 (fully
open),
controlled
according
to
discharge
temperature
Electronic expansion valve B
EXVB
●
●
Four-way valve
ST1
●
●
Off (original)/ On
Four-way valve
ST2
●
●
Off
Four-way valve
ST3
●
●
On
Solenoid valve (liquid refrigerant injection)
SV2
●
●
Only open if discharge temperature > 100
o
C
Solenoid valve (oil balance)
SV4
●
●
Open regularly
Solenoid valve (fast defrosting)
SV5
●
●
Off
Table 3-5.2: Component control during heating operation
Component
Wiring
diagram label
8-12HP
14-16HP
Control functions and states
Inverter compressor A
COMP(INV)
●
●
Controlled according to load requirement
Inverter compressor B
COMP(INV1)
●
DC fan motor A
FANA
●
●
Controlled according to outdoor heat exchanger pipe
temperature
DC fan motor B
FANB
●
●
Electronic expansion valve A
EXVA
●
●
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge superheat
Electronic expansion valve B
EXVB
●
●
Four-way valve
ST1
●
●
On
Four-way valve
ST2
●
●
On
Four-way valve
ST3
●
●
Off
Solenoid valve (liquid refrigerant injection)
SV2
●
●
Only open if discharge temperature > 100
o
C
Solenoid valve (oil balance)
SV4
●
●
Open regularly
Solenoid valve (fast defrosting)
SV5
●
●
Open during defrosting operation
5.2
Compressor Output Control
The compressor rotation speed is controlled according to the load requirement. Before compressor startup, the outdoor
units first estimate the indoor unit load requirement according to the nominal capacity of indoor units currently running,
and then correct for ambient temperature. The compressors then start up according to the corrected load requirement.
During operation the compressors are controlled according to the nominal capacity of indoor units currently running and
the indoor unit heat exchanger temperatures. If the actual load requirement can be provided by one unit alone, then only
one unit starts up. If the actual load requirement requires all outdoor unit modules to operate, the weighted average
actual load requirement is sent to each module and each module operates according to this distributed load
requirement.