The gas connection must be in
accordance with national and local
regulations.
The relevant building regulations
must also be observed.
Natural gas / liquid gas
During installation the gas connection
must be positioned so that it is not
adversely heated when the appliance is
in operation.
Pressure Test Point
a
. This is provided
on the gas regulator (supplied for
natural gas).
^
Loosen the screw in the test point
until it is free in its housing. The
screw is retained in this position.
^
Connect the hose from the pressure
gauge.
^
Reassemble one of the large burners,
turn on the gas and manually light the
burners.
Gas pressure must be set by the
approved gas fitter as shown on the
data plate:
Natural gas
1.0 kPa
ULPG (Propane/Butane)
2.75 kPa
^
Disconnect gauge and screw in the
test point screw.
The Gas Regulator must be set with the
largest burner operating at maximum
setting.
Once the gas cooktop has been
installed it is essential to check that
neither the gas pipe nor the
electricity cable is in contact with hot
parts of the appliance or hot gas
exhaust.
This gas cooktop can be connected
with a class B or D flexible hose,
which complies with AS/NZS 1869
and must be certified. The min. inner
C
must be 10 mm and the maximum
length 1.2 m. Make sure it does not
touch moving parts of the kitchen
furniture, e.g. a drawer.
A full operational test and a test for
possible leakages must be carried
out by the fitter after installation.
Gas connection
41