14
CONFIGURATION Menu
Heading of CONFIGURATION menu. Press Enter to enter submenu
content.
Op parameter Menu
Heading of Op Parameter submenu. Press Enter to enter submenu
content.
This password is required when changing relay settings. Press Enter to
enter a new password. The user needs to enter existing password to
unlock, after that the display shows current password. Press Enter
again to enter the new password.
Model name of this relay
Version of the firmware.
Set the nominal value of the line frequency. Press Enter to change this
value.
Currently active protection group.
CT Ratio Menu
Heading of CT Ratio menu. Press Enter to enter submenu content
Set the rated primary current of the Phase/Line CT.
Set the rated secondary current of the Phase CT according to the CT
input terminal used. This setting affects disturbance record current
scaling only.
Set the rated primary current of the Earth/Ground CT.
Set the rated secondary current of the Earth/Ground Phase CT
according to the CT input terminal used. This setting affects
3.CONFIGURATION
3.1 Op Parameter
Password
****
Description
MK3000L
Firmware
1.0
Frequency
50Hz
3.2 CT Ratio
Phase CT Pri
500A
Earth CT Pri
200A
Active Group
50Hz
Phase CT Sec, In
5A
Earth CT Sec, Ion
1A