42
8.0 Technical Data
RATINGS
Auxiliary Supply
MK3000L-150D
Rated voltage
: 30 ~ 120 V DC
Operating voltage
: 24 ~ 150 V DC
MK3000L-240AD
Rated voltage
: 100 ~ 240 V AC or 140 ~ 340 V DC
Operating voltage
: 85 ~ 265 V AC or 110 ~ 370 V DC
Rated frequency
: 50 or 60Hz
Operating frequency
: 45 ~ 65 Hz
Power consumption
: 8 VA max
Current Inputs
Rated current In
: 1 or 5 A by connection
Frequency
: 50 or 60 Hz nominal
Burden
: < 0.025 VA (1A)
: < 0.3 VA (5A)
Thermal withstand
: 4 x In continuous
: 40 x In for 2s
: 100 x In for 1s
Logic Inputs
Input type
: Optically isolated
Rated voltage
: 20 ~ 380 V DC
: 50 ~ 270 V AC
: (Series resistor 18k Ohm, 2W required for >170 V AC / 240 V DC
direct input)
Output Relay
Trip Contact Relay (R1), R2, IRF Relay
Rated voltage
: 250 V AC/DC
Contact arrangement
: Change-over
Continuous carry
: 5 A
Expected electrical life
: 100,000 operations at rated load
Expected mechanical life : 5 x 10
6
operations
R3,R4
Rated load (resistive)
: 5 A at 250 V AC
: 3 A at 30 V DC
Expected electrical life
: 100,000 operations at rated load
Expected mechanical life : 5 x 10
6
operations
RECORDS
Fault Record
: Up to 50 records.
Event Record
: Up to 250 records
Alarm Record
: Up to 30 records
Disturbance Record
: See Setting Ranges - Disturbance Record