3. Push Buttons

       Reset Button

            • The reset button is for resetting the light indicators (l> or l>>) after an earth-fault

tripping has occured. 

• To reset, press the reset button once.   

 

        Test Button

            • Test button is for checking the relay operation.
            • Push on the test button to simulate an earth-fault low-set and high-set trip condition.

    

4. Trip Contacts

     

       

There is one set of tripping contacts namely, R1.

         

R1

Manual Reset Type

            

•  This contact (R1) is activated during an earth-fault trip. the contacts remain 

                activated regardless of the removal of fault current. This relay can only be reset 

                by pressing the “RESET” button.

5. Electrical Specification

 

Auxiliary Supply

MK201A-240A............................198~265 VAC

MK201A-110A.............................94~127 VAC

Supply frequency.........................50Hz

VA rating......................................3  VA typical

Trip Contact

Rated Voltage.............................250 VAC

Continuous carry.........................5A (cos 

ϕ

  = 1.0)

Expected electrical life................100,000 operations

Expected mechanical life............5 million operations

 

 

 

6. Mechanical 

Indicators
Auxiliary supply...........................Green LED indicator

Pick-up........................................Red LED indicator

Trip..............................................Red LED indicator

Mounting.....................................Panel mounting

Front panel..................................Standard DIN 96x96 mm

Approximate weight....................0.6 kg

Setting Ranges
Low-set (I>).................................0.1A to 2.0A

                    2% to 40%

Low-set delay time (DELAY).......0.05 sec to 1.0 sec

High-set (I>>)..............................I > to 10x I> or disable

High-set delay time (t>>).............instantaneous