3. Push Buttons

       Reset Button

            • The reset button is for resetting the light indicators (l> or l>>) after an overcurrent

tripping has occured. 

• To reset, press the reset button once.   

 

        Test Button

           

 • Test button is for checking the relay operation.

          

  • Push on the test button to simulate an overcurrent low-set and high-set trip condition.

    

4. Trip Contacts

     

       

There is one set of tripping contacts namely, R1.

         

R 1

Manual Reset Type

            •  This contact (R1)  is activated during an overcurrent trip. the contacts remain 

                activated regardless of the removal of fault current. This relay can only be reset 

                by pressing the “RESET” button.

5. Electrical Specification

 

Auxiliary Supply

MK203A-240A......................198~265 VAC

MK203A-110A......................94~127 VAC

Supply frequency..................50Hz

VA rating...............................3  VA typical

Trip Contact

Rated Voltage.......................250 VAC

Continuous carry..................5A (cos 

ϕ

  = 1.0)

Expected electrical life.........100,000 operations

Expected mechanical life......5 million operations

 

 

 

6. Mechanical 

Indicators
Auxiliary supply.....................Green LED indicator

Pick-up..................................Red LED indicator

Trip........................................Red LED indicator

Mounting...............................Panel mounting

Front panel...........................Standard DIN 96x96 mm

Approximate weight..............0.7 kg

Setting Ranges
Low-set (I>)...........................2.0A to 6.0A

                                              40% to 120%

Time multiplier(TM................0.05 to 1.0

High-set(I>>)........................I> to 10 I> or disable

High-set delay time (t>>)......instantaneous