7.0 MODBUS Protocol
7.1 MODBUS Functions
0x03/0x04 Read Input/Holding Registers
Request
Communication address 1 byte
0 to 255
Function code
1 byte
0x03/0x04
Starting Address
2 bytes
0x0000 to 0xFFFF
Quantity of Registers
2 bytes
0x0001 to 0x007d (N)
CRC
2 bytes
2 bytes CRC
Response
Communication address 1 byte
1 to 255
Function code
1 byte
0x03/0x04
Byte count
1 bytes
2 X N
Register value
N X 2 bytes Value
CRC
2 bytes
2 bytes CRC
Error
Communication address 1 byte
1 to 255
Error code
1 byte
0x83/0x84
Exception code
1 bytes
0x01 or 02 or 03 or 04
CRC
2 bytes
2 bytes CRC
*Note: communication address 0 is a broadcast command to
all the slave. The slave will not respond with a broadcast
command.