36
7.2 MODBUS Register
Address
(HEX)
Parameter
Format Unit
Range
Read only. Function 03h or 04h
0000
Device type - main
F1
ASCII
'00'
0001
F1
ASCII
'05'
0002
F1
ASCII
'02'
0003
Device type - sub
F1
ASCII
'01'
0004
Version number - main
F1
ASCII
'XX'
0005
F1
ASCII
'XX'
0006
Version number - sub
F1
ASCII
'XX'
0007
F1
ASCII
'XX'
0008-
000F
Reserved
--
--
--
Measurements and relay status. Read only. Function 03h or 04h
0010
Relay status
F2
Bit field
Bit 0 - 15
0011
Relay LED status
F3
Bit field
Bit 0 - 3
0012
Input status
F4
Bit field
Bit 0
0013
Output status
F5
Bit field
Bit 0 - 2
0014
Active group
F6
--
0=Group 1,
1=Group 2
0015-
001B
Reserved
--
--
--
001C
ILo high word
F8
0.01
Ampere
0-9.99X10
7
(999kA)
001D
ILo low word
001E-
0023
Reserved
--
--
--
0024
ILo Max high word
F8
0.01
Ampere
0-9.99X10
7
(999kA)
0025
ILo Max low word
0026-
002B
Reserved
--
--
--
002C
ILo Avg high word
F8
0.01
Ampere
0-9.99X10
7
(999kA)
002D
ILo Avg low word
002E
Line Frequency
F7
0.01 Hz
0- 10000
(100Hz)
Summary of Contents for x20
Page 1: ...user manual X20 EARTH FAULT RELAY...
Page 2: ...2 EARTH FAULT RELAY Ver 1 00...
Page 7: ...7 7 1 2 Dimension of X20 96mm 96mm 125mm 105mm Front View Side View...
Page 12: ...12 2 3 Wiring With 3 phase 4 wires...
Page 13: ...13 13 With 3 phase 3 wires...
Page 45: ...45 45 Appendix A IDMT Curves Normal Inverse Appendix A...
Page 46: ...46 Very Inverse...
Page 47: ...47 47 Normal Inverse 1 3 10 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05...
Page 48: ...48 Long time Inverse...
Page 49: ...49 49 Extremely Inverse...