38
Address
(HEX)
Parameter
Format Unit
Range
Settings. Read/Write. Function 03h,04h, 06h, 10h
0211
Communication Baud
Rate
F6
--
0=2400,
1=4800,
2=9600,
3=19200,
4=38400
0212
Communication Parity
F6
--
0=None,
1=Odd,
2=Even
0213
Communication Stop Bit
F6
--
0=1bits,
1=2bits
0214
Communication Address
F7
--
1-255
0215
Password
F7
--
0
0216-
022F
Reserved
--
--
--
0230
Cold Load Pickup Level
F7
%
100-500%
0231
Cold Load Pickup tCL
F14
0.01s
10-60000
(600s)
0232
Cold Load Pickup element F15
Bit field
Bit 0-5
0233-
023F
Reserved
--
--
--
0240
Input 1 Function
F6
--
0=None,
1=Aux1,
2=Reserved,
3=Reset,
4=Blocking,
5=Reserved,
6=Group
select,
7=CLPU,
8=Sync
clock. Bit7:
0=Active
high,
1=
Active low
Summary of Contents for x20
Page 1: ...user manual X20 EARTH FAULT RELAY...
Page 2: ...2 EARTH FAULT RELAY Ver 1 00...
Page 7: ...7 7 1 2 Dimension of X20 96mm 96mm 125mm 105mm Front View Side View...
Page 12: ...12 2 3 Wiring With 3 phase 4 wires...
Page 13: ...13 13 With 3 phase 3 wires...
Page 45: ...45 45 Appendix A IDMT Curves Normal Inverse Appendix A...
Page 46: ...46 Very Inverse...
Page 47: ...47 47 Normal Inverse 1 3 10 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05...
Page 48: ...48 Long time Inverse...
Page 49: ...49 49 Extremely Inverse...