11. Specifications 

11.1. 

Possible sensors and measuring ranges 

The following input sensors can be connected for temperature input: 

Sensor type 

Snd parameter 

Standard 

Indication r

ange 

FSR 

Pt100 

rtd 

IEC 751 

-199 C to 850 C 

850 C 

"J"  Fe-CuNi 

FEJ 

IEC 584 

-40 C to 750 C 

750 C 

"K"  NiCr-Ni 

nIC 

IEC 584 

-40 C to 999 C 

999 C 

"L" Fe-CuNi 

FEL 

DIN 43710 

-40 C to 750 C 

750 C 

11.2. 

Electrical specifications 

- Indication accuracy 

 

 

 

 0.25% 

FSR  1 LSD 

@ 25 C

 ambient  0.1% / 10 C 

- Cold junction compensation accuracy   

 0.5 C 

@ 25

C ambient  0.2 C / 10 C 

- Linearization error 

 

 

 

 0.1  C  

- Excitation current (for Pt100)   

 

< 150 A 

- Input current (for thermocouple probes) 

< 1.5 A 

- Sampling rate   

 

 

 

3 - 5 per second 

- Supply voltage  

 

 

 

85 - 250VAC, 50/60Hz 

- Operating temperature  

 

 

0 to 60 C 

- Power consumption 

 

 

 

3VA 

- Degree of protection   

 

 

IP54 front panel, IP20 rear case, IP00 terminals 

- Terminals  

 

 

 

 

fast-on 6.3mm 

- Output relay specification  

 

 

max. 250VAC, 3A (resistive load)  

 

 

 

 

 

 

 

 

electrical durability 1,000,000 operations 

11.3. 

Dimensions 

 

Figure 9 

11.4. 

Ordering information  

Unit type 

Number of outputs 

Dimensions 

MR301 /H 

DIN  H48 x W96 

MR301 /V 

DIN  H96 x W48 

MR302 /H 

DIN  H48 x W96 

MR302 /V 

DIN  H96 x W48 

Summary of Contents for MR301

Page 1: ...EM d o o Bra e Spasi 4A 32000 A AK E mail office mikrorem com tel fax 381 32 370 500 Web www mikrorem com m e r n o r e g u l a c i o n a o p r e m a Digital Temperature Controllers MR301 302 User s M...

Page 2: ...tting the Set Point SP parameter 5 5 2 Setting other parameters 5 6 Overview of some important configuration parameters 5 7 Menus and parametars 6 7 1 Control parameters 7 7 2 Configuration parameters...

Page 3: ...ed value when setting parameters A short press and release one of these buttons causes the transition to the next i e previous menu element or increase decrease the parameter value Holding the button...

Page 4: ...Digital Temperature Controllers MR301 302 4 12 MIKROREM Bra e Spasi 4A A AK Tel fax 381 32 370 500 4 Layout of menus and parameters Figure 2...

Page 5: ...en the upper display shows the name of the desired parameter the lower display shows the parameter value press the M button to access its settings An example of setting the value of parameter Int is g...

Page 6: ...OPr 1 0 to 2 Operator level tAU 1 0 to 5 Digital filter coefficient OFS 1 19 9 to 19 9 C Temperature input shift Lnr 1 0 0 to 99 9 Resistance of connection leads for Pt100 only 6 SPL 1 199 to 999 C SP...

Page 7: ...2 For ON OFF output types marked Lr1 to Lr4 these parameters have the meaning as shown in Figure 6 Shift is relative to the SP which means that a change in SP shifts the transition point itself For ou...

Page 8: ...4A A AK Tel fax 381 32 370 500 Figure 6 Parameter tAU The parameter determines intensity of input signal digital filtering For tAU 0 there is no filtering For tAU 5 filter time constant is approx 8 se...

Page 9: ...o o flash Input signal underrange b b b flash Wire break or input signal overrange flash Measured value is below low limit for chosen sensor flash Measured value is above high limit for chosen sensor...

Page 10: ...ember result for subsequent entry into the tr1 7 Set the parameters Snd FEJ dP On 8 Short connect A1 and A2 terminals Wait for 30 seconds for the measurement to stabilize Remember measured value for s...

Page 11: ...25 FSR 1 LSD 25 C ambient 0 1 10 C Cold junction compensation accuracy 0 5 C 25 C ambient 0 2 C 10 C Linearization error 0 1 C Excitation current for Pt100 150 A Input current for thermocouple probes...

Page 12: ...Digital Temperature Controllers MR301 302 12 12 MIKROREM Bra e Spasi 4A A AK Tel fax 381 32 370 500 12 Notes...

Reviews: