OM-194 473 Page 13
3-7.
Connecting Work Clamp
802 463-A
1
Work Clamp
2
Workpiece
Connect work clamp to a clean,
paint-free location on workpiece, as
close to cutting area as possible.
1
2
3-8.
Connecting Input Power
802 460-B
Check input voltage available at
site.
1
Grounded 120 VAC
Receptacle (Non-CE Models)
A 120 volt, 20 ampere individual
branch circuit protected by
time-delay fuses or circuit breaker
is required (see Section 3-1).
2
Plug From Unit
Select extension cord of 12 AWG
for up to 53 ft (16 m).
3
Grounded 230 VAC
Receptacle (CE Models)
A 230 volt, 10 ampere individual
branch circuit protected by
time-delay fuses or circuit breaker
is required (see Section 3-1).
4
Plug From Unit (Customer
Supplied)
Select extension cord of 14 AWG
for up to 133 ft (41 m).
Y
Special installation may be
required where gasoline or
volatile liquids are present –
see NEC Article 511 or CEC
Section 20.