OM-220979 Page 32

M. Over Current Error

OVER

CRNT

Indicates one or more of the inverter engines has latched with an over-current. Signal is sent from engine module(s) (RC6,

Pin 11, on inverter control board PC1) to process control module PC4 (J2, Pin 6).
The over-current circuit monitors the inverter high frequency transformer primary current. Normal welding will never trip

this circuit, only a fault will cause an over-current condition. LED4 will be lit on the inverter control board, and power must

be cycled to clear this error.

S

The most likely fault to trip this circuit is an open 940 volts DC bus bleeder resistor, either R1 or R8 on the interconnect

board. An open resistor will cause the bus, which is split between two series capacitors, to become unbalanced. The

capacitor with the open resistor will go to approximately 340 volts DC. The other capacitor will go to approximately 600

volts DC. Normally, both capacitors are at approximately 470 volts DC. The unit will weld like this most of the time. A

16 uF balancing capacitor in series with the transformer can keep the transformer from saturating under these adverse

conditions. Occasionally, the inverter transformer will saturate, and when this happens, it draws a huge amount of

current and trips the over-current circuit. This condition locks off the inverter control board and eventually the bus ca-

pacitors will fail. A change to a different resistor eliminated this situation and the problem is no longer an issue.

S

A shorted output diode will cause an over-current error and no weld output will be available.

N. Release Trigger Error

REL

TRIG

Indicates a timed weld has expired, but the trigger is still active. Press Jog/Purge button to clear error.
This error occurs after a timed weld expires and the trigger is not released. A PDA with File Management/WaveWriter

software can be used to set up timed welds. This is strictly an informational

type error.

O. Trigger Stuck Error

TRIG

STUK

Indicates the welding power source was turned on and the trigger signal attempted to weld. Turn welding power source off

and back on again to clear the error.
This error indicates a trigger source was activated while the power source was being powered up. If the trigger source is

removed, the error can be cleared.

S

Use a PDA with ServicePak software and view the Comm Diagnostics screen to see the source of the contactor or

trigger command.

S

If LED2 is lit on RIO board PC10, a contactor signal is being sent from the robot.

P. Wire Feed Speed Error

ERR

WFS

Indicates a wire feed speed error. Press Jog/Purge button to clear error.
This error indicates actual wire feed speed does not match wire feed speed command.

Q. Stop Error

ERR

STOP

Indicates an arc stop error. Press Jog/Purge button to clear error.
This error occurs as a result of obstructions in the wire feed system or a faulty wire drive system. Check wire feed and

wire drive system.

R. Flow Error

ERR

FLOW

Indicates a gas flow error. Press Jog/Purge button to clear error.
This error occurs when there is no gas flow to the gun. Check shielding gas system and reestablish gas flow to the gun.

Summary of Contents for ROI BOX CE

Page 1: ...ROI Remote Operator Interface CE Processes Description MIG GMAW Welding Wire Feeder OM 220979S 2016 02 File Advanced Manufacturing Systems Visit our website at www MillerWelds com ams...

Page 2: ...ntinue the tradition They re just as committed to providing equipment and service that meets the high standards of quality and value established in 1929 This Owner s Manual is designed to help you get...

Page 3: ...Label Location 12 4 2 Unit Specifications 12 4 3 Environmental Specifications 12 SECTION 5 INSTALLATION 13 5 1 Mounting Plate Hole Layout 13 5 2 Installing Insulator Kit 13 5 3 Remote Operator Interf...

Page 4: ...I BOX CE 195383 Council Directives 2014 35 EU Low Voltage 2014 30 EU Electromagnetic Compatibility 2011 65 EU Restriction of the use of certain hazardous substances in electrical and electronic equipm...

Page 5: ...neeling or lying or when there is a high risk of unavoid able or accidental contact with the workpiece or ground For these conditions use the following equipment in order presented 1 a semiautomaticDC...

Page 6: ...ared according to AWS F4 1 and AWS A6 0 see Safety Standards D Do not weld where the atmosphere can contain flammable dust gas or liquid vapors such as gasoline D Connect work cable to the work as clo...

Page 7: ...S can injure D Keep away from moving parts such as fans D Keep all doors panels covers and guards closed and securely in place D Have only qualified persons remove doors panels covers or guards for ma...

Page 8: ...PA Standard 51B from National Fire Protection Association Quincy MA 02269 phone 1 800 344 3555 website www nfpa org OSHA Occupational Safety and Health Standards for General Indus try Title 29 Code of...

Page 9: ...s dans un environnement humideou si l on porte des v tements mouill s sur des structures m talliquestelles que sols grilles ou chafaudages en position coinc e comme assise genoux ou couch e ou s il y...

Page 10: ...br lures Le contact accidentel de l lectrode avec des objets m talliques peut provoquer des tincelles une explosion un sur chauffement ou un incendie Avant de commencer le soudage v rifier et s assur...

Page 11: ...areil D Tenir l quipement c bles et cordons distance des v hicules mobiles lors de toute op ration en hauteur D Suivre les consignes du Manuel des applications pour l quation de levage NIOSH r vis e P...

Page 12: ...ational Electrical Code NFPA Standard 70 from National Fire Protec tion Association Quincy MA 02269 phone 1 800 344 3555 website www nfpa org and www sparky org Safe Handling of Compressed Gases in Cy...

Page 13: ...tion Safe37 2012 05 Wear dry insulating gloves Do not touch electrode with bare hand Do not wear wet or damaged gloves Safe2 2012 05 Protect yourself from electric shock by insulating yourself from wo...

Page 14: ...welding voltage during operation keep hands and metal objects away Safe33 2012 05 Wear hat and safety glasses Use ear protection and button shirt collar Use welding helmet with correct shade of filte...

Page 15: ...urge By Gas Fast Constant Current Circuit Breaker Constant Voltage Slow Trigger Hold Off Trigger Hold On I2 Rated Welding Current Increase Read Instructions U1 Primary Voltage U2 Conventional Load Vol...

Page 16: ...d by the general public as the EMF limits for the general public might be exceeded during welding This equipment is built in accordance with EN 60974 1 and is intended to be used only in an occupation...

Page 17: ...er 1 ROI Control 2 Insulator Plate 3 Mounting Plate 4 1 4 20x3 4 in Screw 4 5 Nylon Shoulder Washer 4 6 3 8 in Flat Washer 4 Place insulator plate between ROI base and metal mounting surface Place nyl...

Page 18: ...ace 2 Swingarc Swivel Assembly 3 Boom 4 AA40G Wire Drive Assembly 5 Trigger Cable 1 2 3 4 5 5 803 698 E 5 4 Connection Diagram 1 Welding Power Source 2 Wire Feeder 3 Gas Cylinder 4 Gas Hose 5 Network...

Page 19: ...ceptacle Information 9 Pin Pin Information A B I C H D G E F A Capacitor C1 to ground B Shield C Volt sense D Can low E Can high F 24 volts DC common G 24 volts DC H Motor voltage 40 volts DC common I...

Page 20: ...play 2 1 Power Source Upper Display Lower Display Axcess Axcs 300 450 675 10 44 Voltage Range Net Wait DTEC OFF Process Setup Adjust Feeder Setup V t A 219 711 A 5 9 Dual Schedule Switch Option 1 Main...

Page 21: ...ing of voltage arc adjust wire feed rate and time value for arc ends DS Dual Schedule Dual Schedule allows selecting a pair of programs that can be used together Feeder Set Up Allow selection of Seque...

Page 22: ...le actual voltage while welding and 3 seconds hold value at end of weld Wire Type Selection of wire type by alloys and classification WFS Term used to represent wire feed speed In MIG mode wire feed s...

Page 23: ...OM 220979 Page 19 6 3 Front Panel Sections See Section 6 5 See Section 6 6 See Section 6 9 See Section 6 8 See Section 6 7 See Section 6 4 Process Setup Adjust Feeder Setup V t A...

Page 24: ...The display will show actual voltage for approximately 3 seconds after welding stops before returning to preset value 2 Upper Display Push Button Press the button to illuminate the LED and allow chan...

Page 25: ...unction and can be adjusted using the Adjust knob 6 Lower Display Push Button 7 Lower Display Push Button LED Pressing the button illuminates the LED and selects either WFS or Arc Ctl value for changi...

Page 26: ...s will exit the Sequence menu and return the system to standby mode 4 Trigger Control LED Press the Feeder Set Up button twice and the Trigger Control LED will illuminate and the upper display will sh...

Page 27: ...n pressing the Process Set Up push button a sixth time will show PROG in the upper display and LOAD in the lower display The new program would be loaded for that particular program in slot 1 thru 8 If...

Page 28: ...s and then ramps up to 700 ipm until trig ger is released or 30 seconds elapses If the gun trigger is still activated after 30 seconds the jog operation is terminated to prevent complete unspooling of...

Page 29: ...Steel 90 Argon 10 CO2 Program 5 MIG 045 Mild Steel 75 Argon 25 CO2 Program 6 Accu pulse 045 Mild Steel 90 Argon 10 CO2 Program 7 Pulse 052 Mild Steel 90 Argon 10 CO2 Program 8 MIG 052 Mild Steel 75 Ar...

Page 30: ...time is set to zero in any timed sequence the sequence is skipped Maximum IPM may actually be lower depending on the process and wire type selection Trigger Pressed Trigger Released Start Time Preflow...

Page 31: ...tenance Disconnect power before maintaining Maintain more often during severe conditions n Check Z Change Clean l Replace To be done by Factory Authorized Service Agent Reference Every 3 Months l Unre...

Page 32: ...R MOTR Section 8 2 F Arc Start Error ERR STRT Section 8 2 G No Tach Error ERR TACH Section 8 2 H Thermal Over Temperature ERR TEMP Section 8 2 I Unknown Error ERR UNKN Section 8 2 J Motor Communicatio...

Page 33: ...software C No Coolant Flow Error ERR COOL Indicates no coolant flow in water flow switch option The error may be reset by reestablishing coolant flow to the gun and then pressing the Jog Purge button...

Page 34: ...r Up Cnt that generated by the boost section of the inverter control board When either of these signals is active RC6 12 is pulled low this is the not ready line out of the inverter control board Shut...

Page 35: ...chassis lifting eye bolts or weld secondary common Measure impedance between chassis and both weld secondary commons Measure the impedance across motor isolation barrier on motor housing All measureme...

Page 36: ...lem is no longer an issue S A shorted output diode will cause an over current error and no weld output will be available N Release Trigger Error REL TRIG Indicates a timed weld has expired but the tri...

Page 37: ...is message appears when RMD and Accuspeed demos are completed Pressing the Jog Purge button will change the screen to CYCL PWR on the display Turn unit power off and back on again RMD and Accuspeed sh...

Page 38: ...OM 220979 Page 34 SECTION 9 ELECTRICAL DIAGRAM Figure 9 1 Circuit Diagram...

Page 39: ...OM 220979 Page 35 214 842 F...

Page 40: ...feeder 1 2 233582 PANEL pc card switch overlay 1 3 212808 BAFFLE pc mounting 1 4 097132 STAND OFF SUPPORT pc card 6 5 PC6 239601 WIRE FEED MODULE 1 6 098691 STAND OFF no 6 32 x 500 lg 250 hex stl m f...

Page 41: ...SKTS service kit 1 PLG4 136810 HOUSING PLUG SKTS service kit 1 PLG81 115092 HOUSING PLUG SKTS service kit 1 PLG10 130203 HOUSING PLUG SKTS service kit 1 PLG50 136810 HOUSING PLUG SKTS service kit 1 PL...

Page 42: ...Notes...

Page 43: ...ns and Subarc SAW Torches Remote Controls and RFCS RJ45 Replacement Parts No labor Roughneck Guns Spoolmate Spoolguns Miller s True Blue Limited Warranty shall not apply to 1 Consumable components suc...

Page 44: ...your personal records Always provide Model Name and Serial Style Number Contact a DISTRIBUTOR or SERVICE AGENCY near you Welding Supplies and Consumables Options and Accessories Personal Safety Equip...

Reviews: