PL-565
Accumass BW500
Page 107
Ba
tc
hing
Batching
The batching process, as it relates to the BW500 operation, can be defined as the
transfer of a predetermined quantity of material.
The process supports a count up operation (P560), in that the total (totalizer 5)
begins at zero and increments up to the programmed setpoint (P564). A relay (RL1
through 5) programmed as the batch setpoint function (P100 = 8) is actuated when
the material total reaches the setpoint. The relay contact acts as an interlock to the
material feed to end the batch.
Another relay can be programmed as a pre-warn alarm (P100 = 7), to alert the
process that batch end is near. The relay is actuated when the material total reaches
the pre-warn setpoint (P567) at some practical value below the batch setpoint). The
pre-warn function is enabled / disabled from the batch process through P566.
For batch operations, the following must be addressed.
✔
connections
✔
programming
✔
operation
Connections
Typical Ladder Logic
BW500 / RL1*
batch stop
batch reset
BW500 / RL2*
pre-warn
stop
alarm
start
24
♦
29
♦
47
48
49
50
motor contactor /
MC1
MC1
* Typical relay assignment. Relays 1 – 5 are
available for batch setpoint or pre-warn alarm
function.
♦
Typical auxiliary input assignment. Inputs 1 – 5
are available for batch reset.
BW500/
aux 1
Summary of Contents for ACCUMASS BW500
Page 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Page 6: ...Page 6 Accumass BW500 PL 565...
Page 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Page 28: ...Page 28 Accumass BW500 PL 565 Installation...
Page 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Page 94: ...Page 94 Accumass BW500 PL 565 Operation...
Page 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Page 110: ...Page 110 Accumass BW500 PL 565 Batching...
Page 112: ...Page 112 Accumass BW500 PL 565 Certification...