For the I/O, the assigned registers represent the logic status (e.g. open or closed) of
the I/O as configured. Discrete inputs are configured via P270, auxiliary input
function; while relay outputs are configured via P100, relay function.
The I/O are mapped into the respective input and output registers, R41,070 and
R41,080, as follows:
R41,070
R41,080
input
bit
output
bit
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
5
5
5
5
For the mA I/O, the assigned registers represent the mA level (e.g. 0 to 20 mA) of the
I/O as registered in P911 and P914, mA output test (output value) and mA input
value.
The mA I/O are mapped into the respective input and output registers:
Input
Register
Output
Register
1
R41,090
1
R41,110
2
R41,091
2
R41,111
3
R41,112
For 0 to 20 mA I/O, the register value ranges from 0 to 20,000. For 4 to 20 mA I/O,
the register value ranges from 4,000 to 20,000. If the 4 or 20 mA values have been
trimmed, then the register value is adjusted accordingly; e.g. an I/O value of 22 mA
would be registered as 22,000.
Diagnostic (R41,200)
Refer to Troubleshooting on page 137
PID Tuning (R41,400 – 41,419)
For BW500 set up for PID control, several registers have been provided for tuning.
Refer to PID Control on page 95 and the associated parameters as listed in the
register map.
Note:
Before you can change any of the setpoints, P799 must be set for remote control.
Summary of Contents for ACCUMASS BW500
Page 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Page 6: ...Page 6 Accumass BW500 PL 565...
Page 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Page 28: ...Page 28 Accumass BW500 PL 565 Installation...
Page 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Page 94: ...Page 94 Accumass BW500 PL 565 Operation...
Page 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Page 110: ...Page 110 Accumass BW500 PL 565 Batching...
Page 112: ...Page 112 Accumass BW500 PL 565 Certification...