Batch Control (P560 – P568)
The following parameters are specific to the use of the BW500 as a batch controller.
Refer to Batch Control.
P560
Batch Mode Control
Enables the batch control function. Batch control is count up.
Entry:
0 = off
f
1 = count up
P564
Batch Setpoint
Sets the batch total. When the amount of material delivered reaches this point, the
batch relay contact opens (P100) to signal the end of the batch.
(
f
=0.000)
Enter the setpoint of the units of weight selected (P005)
P566
Batch Pre-Warn
Enables or disables the pre-warn function associated with batch control, warning that
the batch is nearing completion.
Entry:
0 = off
f
1 = on
P567
Batch Pre-Warn Setpoint
Sets the setpoint for the pre-warn function (P566). When the batch reaches the
setpoint, the relay contact associated with the pre-warn function (P100) closes.
(
f
=0.000)
Enter setpoint in units of weight selected (P005)
P568
Batch Pre-Act
Acts on the batch operation such that when the batch totalizer is reset, the batch total
is compared to the setpoint (P564). The difference is then applied to pre-act on the
setpoint for the next batch in order to improve the accuracy of the batch. The activity
is internally limited to
±
10% of the batch setpoint
Entry:
0 = off
f
1 = Auto
2 = Manual
Summary of Contents for ACCUMASS BW500
Page 1: ...ACCUMASS BW500 Instruction Manual PL 565 January 2001 CCUMASS BW500 33455650 Rev 1 2...
Page 6: ...Page 6 Accumass BW500 PL 565...
Page 12: ...Page 12 Accumass BW500 PL 565 Specifications...
Page 28: ...Page 28 Accumass BW500 PL 565 Installation...
Page 88: ...Page 88 Accumass BW500 PL 565 Parameters...
Page 94: ...Page 94 Accumass BW500 PL 565 Operation...
Page 106: ...Page 106 Accumass BW500 PL 565 PID Control...
Page 110: ...Page 110 Accumass BW500 PL 565 Batching...
Page 112: ...Page 112 Accumass BW500 PL 565 Certification...