Installation
Installation
Note:
Installation shall only be performed by qualified personnel, and in
accordance with local governing regulations.
The following procedure applies to all SPL level monitor installations. See Application
Examples for additional installation requirements. Also, refer to the instruction
manuals of all other equipment connected to the SPL for additional installation
instructions.
AiRanger SPL
Location
Inspect all potential mounting locations. Choose a location suited to the SPL
polycarbonate enclosure and the following location recommendations.
The ideal SPL mounting location:
•
is conformant to the units specifications
•
provides clearance to swing open the front cover and perform the required wiring
connections
•
provides access for viewing
•
is vibration free
Avoid a location that is:
•
exposed to continuous direct sunlight. (Otherwise, provide a sun shield.)
•
close to high voltage or current runs, contactors, or SCR control drives
Cable/Conduit Entry Requirements
Determine the number of enclosure cable/conduit entries required for:
•
Transducer
•
TS-3 temperature sensor (if used)
•
mA output (if used)
•
Relays (if used)
•
Synchronization (see Interconnection/Level System Synchronization)
•
Power
•
Communications: Smartlinx
®
, RS-485, RS-232, bipolar.
Note:
Transducer cable must be run in a grounded metal conduit, separate from other
wiring, (except TS-3 temperature sensor wiring, if applicable).
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...