PL-573
AiRanger SPL
Page 49
Application Par
a
m
.
P210
0/4 mA Setpoint
Use this feature to reference the minimum mA output to any point in the
measurement range.
Enter the material level (referenced to Empty, P006) corresponding to the minimum
mA output.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation
(P001).
Typically, this value is entered in Units (P005) or percent of Span (P007). If mA
Function is set for "volume", enter the value in the Max Volume (P051) units or in
percent of Max Volume.
Values:
-999 to 9999
P211
20 mA Setpoint
Use this feature to reference the 20 mA output to any point in the measurement range.
Enter the material level (referenced to Empty, P006) corresponding to 20 mA.
This feature is preset to 0% or 100% of Span (P007) as determined by Operation
(P001).
Typically, the value is entered in Units (P005) or percent of Span (P007). If mA
Function is set for "volume", enter the value in the Max Volume (P051) units or as a
percent of Max Volume.
Values:
-999 to 9999
P212
mA Min Limit
Use this feature to prevent the mA output from falling below the minimum acceptable
mA input value (preset to 3.800 mA) of the device connected.
Values:
0.000 to 22.00
P213
mA Max Limit
Use this feature to prevent the mA output from exceeding the maximum acceptable
mA input value (preset to 20.20 mA) of the device connected.
Values:
0.000 to 22.00
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...