Page 50
AiRanger SPL
PL-573
Application Par
a
m
.
P214
4 mA Trim
Use this feature (in combination with 20 mA Trim) if the device connected to the mA
output displayed is out of calibration, yet device recalibration is impractical.
Adjust this value (preset to 0.000) as required to make the device connected indicate
4.000 mA when this parameter is accessed.
Values:
-1.00 to 1.000
P215
20 mA Trim
Use this feature (in combination with 4 mA Trim) if the device connected to the mA
output displayed is out of calibration, yet device recalibration is impractical.
Adjust this value (preset to 0.000) as required to make the device connected indicate
20.00 mA when this parameter is accessed.
Values:
-1.00 to 1.000
P219
mA Failsafe
Use this feature if mA output failsafe operation, independent from the Failsafe
Material Level (P071) is desired.
To select an independent mA Failsafe option value:
1. Press
to display the Auxiliary Function symbol,
2. Press
or
to scroll access the failsafe options.
3. Press
, with the desired option displayed.
Values:
"OFF" to have the mA output respond to the Failsafe Material Level (P071).
"HOLd" to hold the output at the "last known" value until normal operation resumes.
"LO" to produce the "Empty" mA output immediately on Failsafe Timer (P070) expiry.
"HI" to produce the "Span" mA output immediately on Failsafe Timer (P070) expiry.
Alternatively, to produce an immediate mA output at a specific value, enter the value
required.
Values:
0.0
to 22.00
Summary of Contents for AiRanger SPL PL-573
Page 1: ...AIRANGER SPL Instruction Manual PL 573 March 2001 IRANGER SPL 33455730 Rev 1 2 ...
Page 8: ...Page 8 AiRanger SPL PL 573 Specifications ...
Page 24: ...Page 24 AiRanger SPL PL 573 Installation ...
Page 86: ...Page 86 AiRanger SPL PL 573 Enhancement Param ...
Page 102: ...Page 102 AiRanger SPL PL 573 Maintenance ...
Page 108: ...Page 108 AiRanger SPL PL 573 Troubleshooting ...