Page 72
AiRanger SPL
PL-573
Enhancement Pa
ra
m.
Advanced Echo Processing
(P810,P816-P825,P830-P835,P840-P845,P850-P852)
Note:
The following Echo Processing parameters are intended for use by authorized
Milltronics Service personnel or Industrial Instrumentation Technicians familiar with
Milltronics ultrasonic echo processing techniques.
Anatomy of an Echo Profile
The relevant parts of an echo profile are listed here. These are visible in either
Dolphin Plus or an oscilloscope.
P810
Scope Displays
Use this feature to monitor the results of Echo Processing parameter alterations.
Connect an oscilloscope to Display Board TP4, TP5, and TP6.
Sweep = 10
µ
s/div. to 1 ms/div. (x 100 for real time); Amplitude = 1 V/div.; Trigger =
external
Observe any combination of the following Scope Displays:
DISPLAY
DISPLAY SYMBOL
P C n u
Echo Profile
TVT Curve
Echo Marker
Echo Lock Window
echo profile
TVT curve
selected echo
echo lock window
echo marker