7ML19981XB83
Pointek ULS200 – QUICK START MANUAL
Page EN-17
m
mmmm
Englis
h
Instructions specific to hazardous area installations (Reference
European ATEX Directive 94/9/EC, Annex II, 1/0/6)
The following instructions apply to equipment covered by certificate number SIRA
00ATEX1205:
1.
The equipment may be used with flammable gases and vapours with apparatus
group IIC and temperature class T5.
2.
The equipment is certified for use in an ambient temperature range of -20 to +60 °C
(-4 to +140 °F).
3.
The equipment has not been assessed as a safety related device (as referred to by
Directive 94/9/EC Annex II, clause 1.5).
4.
Installation and inspection of this equipment shall be carried out by suitably trained
personnel in accordance with the applicable code of practice (EN 60079-14 and EN
60079-17 in Europe).
5.
Repair of this equipment shall be carried out by suitably trained personnel in
accordance with the applicable code of practice (e.g. EN 60079-19 within Europe).
6.
Components to be incorporated into or used as replacements in the equipment shall
be fitted by suitably trained personnel in accordance with the manufacturer’s
documentation.
7.
The certification of this equipment relies upon the following materials used in its
construction:
Aluminum alloy T356 T6 (main enclosure) and A356 T6 (lid)
GE Lexan 943A polycarbonate
Two-part epoxy encapsulant
Silicon based coating
Santoprene 111-55 gasket
Master Bond Polysulphide EP21LPT or Dow Corning 3-4207 encapsulant
(transducer)
ETFE (transducer)
Epoxy syntactic foam (transducer)
If the equipment is likely to come in contact with aggressive substances, then it is
the responsibility of the user to take suitable precautions that prevent it from being
adversely affected, thus ensuring that the type of protection is not compromised.
Aggressive substances:
e.g. acidic liquids or gases that may attack metals, or
solvents that may affect polymeric materials
Suitable precautions:
e.g. regular checks as part of routine inspections or
establishing from the material’s data sheet that it is
resistant to specific chemicals.
8. Equipment Marking:
The equipment marking contains at least the information on the product nameplate,
shown on the inside front cover of this manual.
9. Special Condition for Safe Use: The apparatus must only be supplied from a circuit
containing a suitable rate fuse having a breaking capacity of at least 4000 A.
Summary of Contents for pointek uls200
Page 1: ...Quick Start Manual March 2010 ULS200 pointek...
Page 2: ...IQ300IX fm Page 5 Tuesday October 2 2001 1 43 PM...
Page 20: ...Page EN 18 Pointek ULS200 QUICK START MANUAL 7ML19981XB83 mmmmm English...
Page 38: ...Side DA 18 Pointek ULS200 KVIKSTART MANUAL 7ML19981XB83 mmmmm Dansk...
Page 56: ...Seite DE 18 Pointek ULS200 KURZANLEITUNG 7ML19981XB83 mmmmm Deutsch...
Page 74: ...EL 18 Pointek ULS200 7ML19981XB83 mmmmm...
Page 92: ...P gina ES 18 Pointek ULS200 GU A PARA LA PUESTA EN MARCHA R PIDA 7ML19981XB83 mmmmm Espa ol...
Page 110: ...Page FR 18 Pointek ULS200 MISE EN SERVICE SIMPLIFIEE 7ML19981XB83 mmmmm Fran ais...
Page 128: ...Pagina IT 18 Pointek ULS200 MANUALE PER L AVVIO RAPIDO 7ML19981XB83 mmmmm Italiano...
Page 146: ...Pagina NL 18 Pointek ULS200 QUICK START HANDLEIDING 7ML19981XB83 mmmmm Nederlands...
Page 164: ...P gina PT 18 Pointek ULS200 MANUAL DE ARRANQUE R PIDO 7ML19981XB83 mmmmm Portugu s...
Page 182: ...Sivu SU 18 Pointek ULS200 PIKAK YTT OPAS 7ML19981XB83 mmmmm Suomi...
Page 200: ...Sida SV 18 Pointek ULS200 MANUAL F R SNABBSTART 7ML19981XB83 mmmmm Svenska...