C7 parameter group setting for 22/15 HP models using VS-626M5-11KW Inverter
and VS-656MR5-15KW Converter
5-20-02
A handheld digital operator is required to access this parameter group. These parameters should be
setup prior to shipping a drive into the field for service replacement.
Using a handheld digital operator follow the steps outlined below
1. Enter standard motor code for 22/15 dual speed motor
2. Cycle
power
3. Set parameter C1-25 to 0FF
4. Set parameter C1-59 bit 7 = 1 (1 X X X X X X X) to allow access to the C1-8X parameters.
5. Set parameter C1-88 bit 6 = 1 (X 1 X X X X X X) to allow access to the C7 parameter group.
6. Set C7 parameters per custom list below.
Note: Cycling power in step 7 will reset parameters C1-59 and C1-88, so be sure that all programming is
completed before cycling power in step 7.
7. Cycle
power
Parameter #
Value
C7-01 1750
C7-02 1.27
C7-03 46.7
C7-04 19.6
C7-05 4000
C7-06 0.59
C7-07 168
C7-08 105.3
C7-09 105.3
C7-10 103.1
C7-11 101.4
C7-12 95.9
C7-13 0.7
C7-14 1.3
C7-15 2.0
C7-16 2.7
C7-22 62
Parameter #
Value
C7-23 12.9
C7-26 1750
C7-31 600
C7-32 1.50
C7-33 49.0
C7-34 16.5
C7-35 600
C7-37 136
C7-38 109.7
C7-39 112.0
C7-40 108.4
C7-41 106.6
C7-42 78.8
C7-47 10.0
Parameter #
Value
C7-48 10.0
C7-49 10.0
C7-50 10.0
C7-52 54
C7-53 11.0
C7-56 600
C7-61 8000
C7-67 0.0476
C7-68 0.626
C7-70 4000
C7-72 83.8
C7-73 00000000