background image

MILPOWER SOURCE                                                     

110BA1UM, REV(B)

9

6.

Operation, Controls and Indicators   (ref. Figures 4 and 5)

6.1

Turning the UPS ON and OFF

In order to turn the UPS ON (after an electrical connection is made), turn ON the Input ON/OFF
switch (4), the Master ON/OFF switch (5) and the remote ON/OFF switch. (The order is not
important). If remote ON/OFF is not used, the connections of J5 (described in para. 8.3) should be
installed before the unit is turned on.

When the Master ON/OFF switch  (5) or the remote ON/OFF switch are turned off, the internal
contactors open and disconnect both the input and the output of the UPS and it turns OFF.

When the UPS operates, turning off the Input ON/OFF switch (4) disconnects the UPS from the AC
input, and the UPS then runs on battery power only.

To turn the UPS off, the Master ON/OFF switch or the remote ON/OFF switch must be in the OFF
position. (It will automatically disconnect the input connector too).

Note:  The UPS will not start on battery power (to avoid battery discharge during shipping and
storage).  Hence, the Input ON/OFF switch must be ON and AC voltage must be present at the input
in order to start the UPS.

When a remote control of the UPS is desired, the Input ON/OFF and the Master ON/OFF switches
on the front panel should be both in the ON position. Turning the remote ON/OFF switch ON and
OFF will turn the UPS ON and OFF. (Please see paragraph 8.3).

6.2

Visual Indicators

6.2.1

Normal Operation

When the UPS is running on AC input power and both Master and Input switches are ON, the two
bar graphs (17, 18), the green Input OK LED (7) and the green Output OK LED (9) are on.

The Load Level Bar Graph (17) indicates the loading percentage of the UPS.  100% load is equal to
1500W of output power.  The lower six positions of the Load Level Bar Graph (15% to 75%) are
green.  The next three positions (80%, 110%, 120%) are orange and the two uppermost positions
(130% and 140%) are red.  The colors do not have any special significance and are only intended to
assist fast scanning of the load level.

The Battery Charge Bar Graph (18) indicates the percentage charge level of the battery.  100%
signifies that at least 10 minutes of full load will be supported by the battery, 50% signifies
5 minutes at full load and so on. Lower loads result in longer expected battery operation time.
When the battery is being charged, the uppermost active segment of the Battery Charge Bar Graph
blinks to indicate that charging is on.

6.2.2

Standby Mode

When the yellow Output Standby LED (8) is on, the UPS is in the Standby Mode. In this Mode the
DC-AC inverter is OFF and the output contactor is open, but all other function of the UPS are active
(including battery charging and RS-232 communication port). The UPS reaches this mode when
command by the RS-232 or the “dry relays” into this mode.

Summary of Contents for M110BA-1

Page 1: ...IN THE U S A USER S MANUAL East Coast Milpower Source 7 Field Lane RTE 106 Belmont NH 03220 Phone 603 267 8865 Fax 603 267 7258 West Coast Hytech Associates 1498 Linda Vista Ave Pasadena CA 91103 Pho...

Page 2: ...st 11 7 Taking Care of the Battery 11 7 1 Battery Service Life 11 7 2 Replacing the Battery Pack 12 8 Communications and Remote Control 13 8 1 Dry Contacts Interface 13 8 1 1 Option 0 Standard Dry Con...

Page 3: ...ched off by the Input ON OFF Switch The unit should only be plugged into an approved double pole and fused 20A electrical outlet for 230VAC input use 15 AMP fuses The Replaceable Battery Pack of the M...

Page 4: ...le Battery Pack a Battery Charger a DC AC Inverter and a microcontroller based Control Circuit The AC DC Converter is a high frequency switching converter that provides 320VDC to the DC AC inverter Th...

Page 5: ...VARISTOR AC DC CONVERTER DC AC INVERTER CONTROL MONITOR BATTERY CHARGER BATTERY PACK 24VDC 24VRTN INPUT ON OFF SWITCH MASTER ON OFF SWITCH REMOTE ON OFF SWITCH 2 POLES INPUT CONTACTOR 2 POLES OUTPUT...

Page 6: ...inning of this manual Make sure that the input voltage setting is correct Make sure that the Master switch is in the OFF position Two circular connectors J1 and J2 are provided on the rear panel of th...

Page 7: ...1 PWR COND OUT 1 PWR COND OUT 2 UPS OUT 1 NEUT UPS OUT 2 HOT 115VAC VIA TWO POLE CIRCUIT BREAKER AC TO LOAD BYPASS SELECTOR NOTE 2 GND CHASSIS G E C D A B F UPS NOTE 3 SAFETY GND REAR PANEL GND CONN...

Page 8: ...A J1 PWR COND INPUT PHASE 2 PWR COND INPUT PHASE 1 CHASSIS GND UPS OUT 1 NEUT UPS OUT 2 HOT 115VAC VIA TWO POLE CIRCUIT BREAKER GND CHASSIS G E C D A B F UPS NOTE 2 SAFETY GND REAR PANEL GND CONN NOTE...

Page 9: ...el Main Components See Figure 4 1 Removable air filter of the Power Conditioner s cooling air 2 Visual Indicators and Switches for detailed view see Figure 5 3 Air Inlet of main UPS heatsink 4 Input O...

Page 10: ...2 Alarm Off Push button 13 Low Battery Warning LED blinking yellow 14 Overload Shutdown LED red 15 Overtemperature Warning LED blinking yellow 16 Overtemperature Shutdown LED red 17 Load Level Bar Gra...

Page 11: ...onnector see Figure 2 for pin out 25 J2 Output Power Connector see Figure 2 for pin out 26 GND Connection 27 Dry Contacts Connector J3 see paragraph 8 for pin out description 28 RS232 Connector J4 see...

Page 12: ...the remote ON OFF switch ON and OFF will turn the UPS ON and OFF Please see paragraph 8 3 6 2 Visual Indicators 6 2 1 Normal Operation When the UPS is running on AC input power and both Master and Inp...

Page 13: ...n circuit and shuts down the UPS When the input AC voltage recovers the UPS will turn on automatically 6 2 4 Overload Condition If the load exceeds the rating of the UPS or there is a short circuit on...

Page 14: ...ess it is a Limited Life Item and its life expectancy depends upon its operating and storage conditions The three most important factors that determine the life of the battery are Temperature Storage...

Page 15: ...ccess cover Remove screws e Disconnect the connector by pulling upward f Unscrew the right battery s screws on the top and three screws on the right side of the UPS marked by a B on the top and recess...

Page 16: ...attery Operation 3 5 System Common Ground 6 N C 7 O Battery Voltage Low 4 8 O UPS On 5 9 O Input Power Loss Battery operation 3 Notes to Table 1 1 Pin 1 is shorted to pin 2 when any one of the followi...

Page 17: ...otes to Table 2 1 Connecting 5 to 12Vdc to pin 6 to pin 1 causes the UPS to shutdown if in Battery Mode latched 2 If AC input is good pin 7 is shorted to pin 2 and pin 3 is open If AC input is bad pin...

Page 18: ...lly shorted to J3 pin 9 not used by RS232 link 8 3 Remote ON OFF Interface J5 Important note The M110BA 1 is shipped with a matting connector plugged into J5 with a jumper that enables the unit If rem...

Page 19: ...oltage Rating Frequency Waveform 115Vac 3 grounded neutral see Note 1 2000VA 1000W 60Hz 0 2 digitally synthesized from a crystal oscillator Sinusoidal THD 2 linear load 4 non linear BATTERY Type Capac...

Page 20: ...Input Fail status lamps On Batt status lamp Batt Passed and Batt Failed lamps for battery self test Low Batt warning lamp Overload Shutdown status lamp Overtemp warning and Overtemp Shutdown lamps Whe...

Page 21: ...rge Level status of all User Programmable Options and failure diagnostic Commands UPS Shutdown UPS Standby Initiate Battery Test Enable Disable Periodic Battery Test Enable Disable Battle Mode Enable...

Reviews: