MILPOWER SOURCE                                                     

110BA1UM, REV(B)

11

6.3

Battery Test

Battery Test may be invoked only if the UPS runs on AC input power, the Battery Charge level is
above 85%, the load is above 35% and the battery is not engaged in supporting Input Power Limit.

If Battery Test is denied due to low charge level, the Charge Level Bar Graph blinks once when the
Battery Test Push-button is pressed.

To test the battery, press momentarily on the Battery Test Push-button (21).  The green Battery Test
Passed LED (20) will blink for about 3 seconds (indicating that Battery Test is running).  After about
3 seconds, either the red Battery Test Failed LED (22) will turn on (and latch), indicating a bad
battery, or the green Battery Test Passed LED (20) will turn on for about 20 seconds, indicating that
battery successfully passed the test.

The Battery Test may be repeated only after at least 20 seconds have elapsed since the last test.

7.

Taking Care of the Battery

7.1

Battery Service Life

The gel lead-acid, sealed and maintenance-free battery used in the M110BA-1 is of the highest
quality.  Nevertheless, it is a Limited Life Item, and its life expectancy depends upon its operating
and storage conditions.
The three most important factors that determine the life of the battery are:

Temperature
Storage Conditions
Charge-Discharge Cycles

Temperature
The battery used in the M110BA-1 is sealed and does not “dry up” or lose gasses, but its end of
service life is brought about by the gradual corrosion of the electrodes.  This process is
accelerated by high operating temperatures.  Every 10°C rise above 20°C will reduce the battery
service life by half.

Storage Conditions
When lead-acid batteries are stored for extended periods of time, lead sulfate is formed on the
negative plates and insulates them.
The sulfating rate depends on the ambient temperature and the charge level of the battery.  High
temperature and low charge level accelerate the sulfating and reduce the battery life.
In order to protect your battery from damage during storage:

 

Make sure the battery is fully charged periodically (every 4 months if the temperature is
approximately 24°C, and every two months if the temperature is higher than 37°C) by operating
the UPS for at least four hours.

 

Store the batteries in a cool place (may be stored separately from the UPS).

 

Never store a discharged battery !!!

Summary of Contents for M110BA-1

Page 1: ...IN THE U S A USER S MANUAL East Coast Milpower Source 7 Field Lane RTE 106 Belmont NH 03220 Phone 603 267 8865 Fax 603 267 7258 West Coast Hytech Associates 1498 Linda Vista Ave Pasadena CA 91103 Pho...

Page 2: ...st 11 7 Taking Care of the Battery 11 7 1 Battery Service Life 11 7 2 Replacing the Battery Pack 12 8 Communications and Remote Control 13 8 1 Dry Contacts Interface 13 8 1 1 Option 0 Standard Dry Con...

Page 3: ...ched off by the Input ON OFF Switch The unit should only be plugged into an approved double pole and fused 20A electrical outlet for 230VAC input use 15 AMP fuses The Replaceable Battery Pack of the M...

Page 4: ...le Battery Pack a Battery Charger a DC AC Inverter and a microcontroller based Control Circuit The AC DC Converter is a high frequency switching converter that provides 320VDC to the DC AC inverter Th...

Page 5: ...VARISTOR AC DC CONVERTER DC AC INVERTER CONTROL MONITOR BATTERY CHARGER BATTERY PACK 24VDC 24VRTN INPUT ON OFF SWITCH MASTER ON OFF SWITCH REMOTE ON OFF SWITCH 2 POLES INPUT CONTACTOR 2 POLES OUTPUT...

Page 6: ...inning of this manual Make sure that the input voltage setting is correct Make sure that the Master switch is in the OFF position Two circular connectors J1 and J2 are provided on the rear panel of th...

Page 7: ...1 PWR COND OUT 1 PWR COND OUT 2 UPS OUT 1 NEUT UPS OUT 2 HOT 115VAC VIA TWO POLE CIRCUIT BREAKER AC TO LOAD BYPASS SELECTOR NOTE 2 GND CHASSIS G E C D A B F UPS NOTE 3 SAFETY GND REAR PANEL GND CONN...

Page 8: ...A J1 PWR COND INPUT PHASE 2 PWR COND INPUT PHASE 1 CHASSIS GND UPS OUT 1 NEUT UPS OUT 2 HOT 115VAC VIA TWO POLE CIRCUIT BREAKER GND CHASSIS G E C D A B F UPS NOTE 2 SAFETY GND REAR PANEL GND CONN NOTE...

Page 9: ...el Main Components See Figure 4 1 Removable air filter of the Power Conditioner s cooling air 2 Visual Indicators and Switches for detailed view see Figure 5 3 Air Inlet of main UPS heatsink 4 Input O...

Page 10: ...2 Alarm Off Push button 13 Low Battery Warning LED blinking yellow 14 Overload Shutdown LED red 15 Overtemperature Warning LED blinking yellow 16 Overtemperature Shutdown LED red 17 Load Level Bar Gra...

Page 11: ...onnector see Figure 2 for pin out 25 J2 Output Power Connector see Figure 2 for pin out 26 GND Connection 27 Dry Contacts Connector J3 see paragraph 8 for pin out description 28 RS232 Connector J4 see...

Page 12: ...the remote ON OFF switch ON and OFF will turn the UPS ON and OFF Please see paragraph 8 3 6 2 Visual Indicators 6 2 1 Normal Operation When the UPS is running on AC input power and both Master and Inp...

Page 13: ...n circuit and shuts down the UPS When the input AC voltage recovers the UPS will turn on automatically 6 2 4 Overload Condition If the load exceeds the rating of the UPS or there is a short circuit on...

Page 14: ...ess it is a Limited Life Item and its life expectancy depends upon its operating and storage conditions The three most important factors that determine the life of the battery are Temperature Storage...

Page 15: ...ccess cover Remove screws e Disconnect the connector by pulling upward f Unscrew the right battery s screws on the top and three screws on the right side of the UPS marked by a B on the top and recess...

Page 16: ...attery Operation 3 5 System Common Ground 6 N C 7 O Battery Voltage Low 4 8 O UPS On 5 9 O Input Power Loss Battery operation 3 Notes to Table 1 1 Pin 1 is shorted to pin 2 when any one of the followi...

Page 17: ...otes to Table 2 1 Connecting 5 to 12Vdc to pin 6 to pin 1 causes the UPS to shutdown if in Battery Mode latched 2 If AC input is good pin 7 is shorted to pin 2 and pin 3 is open If AC input is bad pin...

Page 18: ...lly shorted to J3 pin 9 not used by RS232 link 8 3 Remote ON OFF Interface J5 Important note The M110BA 1 is shipped with a matting connector plugged into J5 with a jumper that enables the unit If rem...

Page 19: ...oltage Rating Frequency Waveform 115Vac 3 grounded neutral see Note 1 2000VA 1000W 60Hz 0 2 digitally synthesized from a crystal oscillator Sinusoidal THD 2 linear load 4 non linear BATTERY Type Capac...

Page 20: ...Input Fail status lamps On Batt status lamp Batt Passed and Batt Failed lamps for battery self test Low Batt warning lamp Overload Shutdown status lamp Overtemp warning and Overtemp Shutdown lamps Whe...

Page 21: ...rge Level status of all User Programmable Options and failure diagnostic Commands UPS Shutdown UPS Standby Initiate Battery Test Enable Disable Periodic Battery Test Enable Disable Battle Mode Enable...

Reviews: