background image

MILPOWER SOURCE                                                     

110BA1UM, REV(B)

17

9.

Specifications (continued)

ENVIRONMENT

Temperature

Humidity

Altitude

Orientation

Mechanical
shock

Vibration

Non operating: -40 to +72

°

C

Note:  High temperature for prolonged duration will shorten the battery life.
Operating:   0  to +52

°

C.

Up to 95%.

Operating: Up to 10,000 feet.
Non-operating:  (Air transport)  40,000 feet.

May be installed at any orientation.

When packed, withstands the free fall drop and edgewise drop IAW
Methods 5007.1 and 5008.1 of Federal Test Method standard 101C.
When  operating, withstands the high-impact shipboard shock IAW
MIL-S-901D, grade A, class  II., Type B.

When operating, withstands Type I vibration IAW MIL-STD-167-1. The
UPS will endure a sweep of 1.5g sinusoidal vibration from 5 to 50 Hz for a
total duration of 2 hours, and random vibration IAW MIL-STD-810D,  Cat.
9, Proc. I (test condition I-3.2.11, Fig. 514.3-34)

INDICATIONS
& CONTROLS

a) Visual
Indications
(Front panel)

b) Test Mode

c)  Audible
Alarm

d) Power
Switches

e) Remote
ON/OFF

10-segment tri-color Bar Graph for load level display.
10-segment Bar Graph for battery charge level display.
"Output OK", "Output Fail" and “Standby” status lamps.
"Input OK"  and "Input Fail" status lamps.
"On Batt " status lamp.
"Batt Passed" and "Batt Failed" lamps for  battery  self-test.
"Low Batt" warning lamp.
"Overload  Shutdown"  status lamp.
"Overtemp warning" and "Overtemp Shutdown" lamps.

When test mode is invoked by pressing the push-button on the front panel,
the UPS performs battery impedance testing without interrupting the output
power  (even if the battery fails) utilizing a proprietary time-sharing circuit.
The test results are displayed on  panel indicators.
End-to-End testing of the UPS is accomplished by cycling the INPUT
ON/OFF switch on the front panel.

The UPS will beep when it operates on battery power or during over-
temperature condition.  The alarm may be silenced by pressing the "Alarm
Off" push-button on the front panel.

The M110BA-1 has two double-pole contactors, one on the input and one on
the output.
The input ON/OFF contactor is controlled by the input ON/OFF switch
located on the front panel.
The Master ON/OFF switch, located on the front panel, shuts down the UPS
and opens both input and output contactors when in the OFF position.

 When the two ON/OFF pins are opened the UPS will turn OFF and the
input and output contactors will open. When the two lines are shorted
together the front panel switches determine the status. (The UPS is supplied
with a mating connector and a jumper between the two ON/OFF pins).

Summary of Contents for M110BA-1

Page 1: ...IN THE U S A USER S MANUAL East Coast Milpower Source 7 Field Lane RTE 106 Belmont NH 03220 Phone 603 267 8865 Fax 603 267 7258 West Coast Hytech Associates 1498 Linda Vista Ave Pasadena CA 91103 Pho...

Page 2: ...st 11 7 Taking Care of the Battery 11 7 1 Battery Service Life 11 7 2 Replacing the Battery Pack 12 8 Communications and Remote Control 13 8 1 Dry Contacts Interface 13 8 1 1 Option 0 Standard Dry Con...

Page 3: ...ched off by the Input ON OFF Switch The unit should only be plugged into an approved double pole and fused 20A electrical outlet for 230VAC input use 15 AMP fuses The Replaceable Battery Pack of the M...

Page 4: ...le Battery Pack a Battery Charger a DC AC Inverter and a microcontroller based Control Circuit The AC DC Converter is a high frequency switching converter that provides 320VDC to the DC AC inverter Th...

Page 5: ...VARISTOR AC DC CONVERTER DC AC INVERTER CONTROL MONITOR BATTERY CHARGER BATTERY PACK 24VDC 24VRTN INPUT ON OFF SWITCH MASTER ON OFF SWITCH REMOTE ON OFF SWITCH 2 POLES INPUT CONTACTOR 2 POLES OUTPUT...

Page 6: ...inning of this manual Make sure that the input voltage setting is correct Make sure that the Master switch is in the OFF position Two circular connectors J1 and J2 are provided on the rear panel of th...

Page 7: ...1 PWR COND OUT 1 PWR COND OUT 2 UPS OUT 1 NEUT UPS OUT 2 HOT 115VAC VIA TWO POLE CIRCUIT BREAKER AC TO LOAD BYPASS SELECTOR NOTE 2 GND CHASSIS G E C D A B F UPS NOTE 3 SAFETY GND REAR PANEL GND CONN...

Page 8: ...A J1 PWR COND INPUT PHASE 2 PWR COND INPUT PHASE 1 CHASSIS GND UPS OUT 1 NEUT UPS OUT 2 HOT 115VAC VIA TWO POLE CIRCUIT BREAKER GND CHASSIS G E C D A B F UPS NOTE 2 SAFETY GND REAR PANEL GND CONN NOTE...

Page 9: ...el Main Components See Figure 4 1 Removable air filter of the Power Conditioner s cooling air 2 Visual Indicators and Switches for detailed view see Figure 5 3 Air Inlet of main UPS heatsink 4 Input O...

Page 10: ...2 Alarm Off Push button 13 Low Battery Warning LED blinking yellow 14 Overload Shutdown LED red 15 Overtemperature Warning LED blinking yellow 16 Overtemperature Shutdown LED red 17 Load Level Bar Gra...

Page 11: ...onnector see Figure 2 for pin out 25 J2 Output Power Connector see Figure 2 for pin out 26 GND Connection 27 Dry Contacts Connector J3 see paragraph 8 for pin out description 28 RS232 Connector J4 see...

Page 12: ...the remote ON OFF switch ON and OFF will turn the UPS ON and OFF Please see paragraph 8 3 6 2 Visual Indicators 6 2 1 Normal Operation When the UPS is running on AC input power and both Master and Inp...

Page 13: ...n circuit and shuts down the UPS When the input AC voltage recovers the UPS will turn on automatically 6 2 4 Overload Condition If the load exceeds the rating of the UPS or there is a short circuit on...

Page 14: ...ess it is a Limited Life Item and its life expectancy depends upon its operating and storage conditions The three most important factors that determine the life of the battery are Temperature Storage...

Page 15: ...ccess cover Remove screws e Disconnect the connector by pulling upward f Unscrew the right battery s screws on the top and three screws on the right side of the UPS marked by a B on the top and recess...

Page 16: ...attery Operation 3 5 System Common Ground 6 N C 7 O Battery Voltage Low 4 8 O UPS On 5 9 O Input Power Loss Battery operation 3 Notes to Table 1 1 Pin 1 is shorted to pin 2 when any one of the followi...

Page 17: ...otes to Table 2 1 Connecting 5 to 12Vdc to pin 6 to pin 1 causes the UPS to shutdown if in Battery Mode latched 2 If AC input is good pin 7 is shorted to pin 2 and pin 3 is open If AC input is bad pin...

Page 18: ...lly shorted to J3 pin 9 not used by RS232 link 8 3 Remote ON OFF Interface J5 Important note The M110BA 1 is shipped with a matting connector plugged into J5 with a jumper that enables the unit If rem...

Page 19: ...oltage Rating Frequency Waveform 115Vac 3 grounded neutral see Note 1 2000VA 1000W 60Hz 0 2 digitally synthesized from a crystal oscillator Sinusoidal THD 2 linear load 4 non linear BATTERY Type Capac...

Page 20: ...Input Fail status lamps On Batt status lamp Batt Passed and Batt Failed lamps for battery self test Low Batt warning lamp Overload Shutdown status lamp Overtemp warning and Overtemp Shutdown lamps Whe...

Page 21: ...rge Level status of all User Programmable Options and failure diagnostic Commands UPS Shutdown UPS Standby Initiate Battery Test Enable Disable Periodic Battery Test Enable Disable Battle Mode Enable...

Reviews: